E L C O p e r a t i o n M a n u a l
F o r m o r e i nf o r m a t i o n v i sit :
w w w. e a t o n . c o m
MN05003006E
1-136
y
M0 = On: Disable CH6 configuration changes
3. Program
Description
y
When X0 = On, write K1 (H’0001) to CR#7 to configure CH6 for mode 1 (current
output mode).
y
When X1 = On, write K9,600 (Offset value for CH6) into CR#33 and K20,800 (Gain
value for CH6) into CR#39.
y
When X1 goes from On to Off, set M0 = On to disable configuration changes to the
D/A conversion curve. Write K32 (H’20) into CR#40 b5=1.
4. Program
example
Ladder diagram:
Explanation:
Set CH6 to mode 1 (current
output mode)
Set the Offset value for CH6
Set the Gain value for CH6
X0
M0
X1
K0
K39
K1
K0
K40
K1
K0
K1
TOP
K0
K1
M0
TOP
TOP
TOP
X1
SET
H1
K9600
K20800
H20
K7
K33
Disable CH6 configuration
changes