E L C O p e r a t i o n M a n u a l
F o r m o r e i nf o r m a t i o n v i sit :
w w w. e a t o n . c o m
MN05003006E
1-122
Description
bit11=1
CH4 exceeds upper limit
bit12=1
CH5 exceeds upper limit
bit13=1
CH6 exceeds upper limit
bit14 ~ bit15
Reserved
C R # 1 0 2 , 1 0 3 , 1 0 4 , 1 0 5 , 1 0 6 , 1 0 7 :
Configuration value for CH1 ~ CH6 upper limit
Set the upper limit value for CH1 ~ CH6. Default: K32,000
C R # 1 0 8 , 1 0 9 , 11 0 , 111 , 11 2 , 11 3 :
Configuration value for CH1 ~ CH6 lower limit
Set the lower limit value for CH1 ~ CH6. Default: -32,000
C R # 11 4 , 11 5 :
Output update time for CH5~ CH6
Unit: 100ms
Range
Default
1~100 (0.1s~10s)
0
C R # 11 8 :
LV output mode configuration for CH5 ~ CH6. Default=0
CR[118]=0: When the power is in a LV (low voltage) condition, the output performs natural
discharge.
CR[118]=1: When the power is in a LV condition, set the output value to 0. See the curve
below:
Содержание ELCM Series
Страница 1: ......
Страница 107: ...ELC Operation Manual For more information visit www eaton com MN05003006E 2 20 MEMO...