E L C O p e r a t i o n M a n u a l
F o r m o r e i nf o r m a t i o n v i sit :
w w w. e a t o n . c o m
MN05003006E
1-104
Offset (CR#34 ~ CR#37)
The corresponding voltage output value when the
digital input value = 0.
Range of digital conversion -32,000 ~ +32,000
Max./Min. input range of
digital data
-32,768 ~ +32,767
Current Output Mode1
z
Mode 1 (H’0001): (0mA ~ +20mA)
20m A
+3 2,000
0
Offs et
Gai n
+1 6,000
10m A
C urren t
output
D igita input
l
+3 2,767
Mode 1 of CR#2~ CR#5
0mA ~ +20mA, Gain = 10mA (16,000), Offset = 0mA
(0).
Gain (CR#28 ~ CR#31)
The corresponding current output value when the
digital input value = 16,000.
Offset (CR#34 ~ CR#37)
The corresponding current output value when the
digital input value = 0.
Range of digital conversion 0 ~ +32,000
Max./Min. range of digital
data
0 ~ +32,767
z
Mode 2 (H’0002): (4mA ~ +20mA)
20m A
+3 2,000
0
Offset
4m A
+1 6,000
12m A
C urren t
outpu t
D igita inpu t
l
Gai n
+3 2,767
-6,40 0
Mode 2 of CR#2~ CR#5
4mA ~ +20mA, Gain = 12mA (19,200), Offset = 4mA
(6,400).
Gain (CR#28 ~ CR#31)
The corresponding current output value when the
digital input value = 19,200.
Offset (CR#34 ~ CR#37)
The corresponding current output value when the
digital input value = 6,400.
Range of digital conversion 0 ~ +32,000
Max./Min. input range of
digital data
-6400 ~ +32,767
Содержание ELCM Series
Страница 1: ......
Страница 107: ...ELC Operation Manual For more information visit www eaton com MN05003006E 2 20 MEMO...