E L C O p e r a t i o n M a n u a l
F o r m o r e i nf o r m a t i o n v i sit :
w w w. e a t o n . c o m
MN05003006E
1-166
C R # 4 2 :
Function: Return to default setting, Default = H’0000
Description
bit0
b0=0, no action on CH1; b0=1, set CH1
to default settings
bit1
b1=0, no action on CH2; b1=1, set CH2 to default settings
bit2
b2=0, no action on CH3; b2=1, set CH3 to default settings
bit3
b3=0, no action on CH4; b3=1, set CH4 to default settings
bit4 ~ bit15
Reserved
Note: Set the designated bit to 1 and the corresponding channel will be returned to default
settings. When complete, the value will be set to 0. If CR#40 (prohibit configuration changes)
is enabled, CR#42 will be invalid, and all configured values will remain unchanged and Error
Code bit 12 of CR#43 will be set to 1
Relative Parameters
CR#2 ~ CR#5
Input mode for CH1 ~ CH4
CR#8 ~ CR#11
Number of samples for CH1 ~ CH4
CR#28 ~ CR#31
Offset settings for CH1 ~ CH4
CR#100
Function: Enable/Disable limit detection
CR#102~CR#105
Upper limit values for CH1~CH4
CR#108~CR#111
Lower limit values for CH1~CH4
CR#120~CR#196 PID
settings
C R # 4 3 :
Error status. Default=H’0000
CR#43: error status value. See the table below:
Description
bit0 K1 (H’1)
Power supply error
bit6
K64 (H’40)
CH4 Conversion error
bit1 K2 (H’2)
Hardware error
bit9
K512(H’0200)
Mode setting error
bit2 K4 (H’4)
Upper / lower limit error
bit10 K1024(H’0400)
Number of samples
error
bit3 K8 (H’8)
CH1 Conversion error
bit11 K2048(H’0800)
Upper / lower limit
configuration error
bit4 K16 (H’10)
CH2 Conversion error
bit12 K4096(H’1000)
Configuration changes
prohibited
bit5 K32 (H’20)
CH3 Conversion error
bit13 K8192(H’2000)
Communication fault on
next module
Note: Each error status is determined by the corresponding bit (b0 ~ b13) and there may be more
than 2 errors occurring at the same time. 0 = normal; 1 = error