E L C O p e r a t i o n M a n u a l
F o r m o r e i nf o r m a t i o n v i sit :
w w w. e a t o n . c o m
MN05003006E
1-128
z
Mode 6 (H’0006): (+4mA ~ +20mA)
+32000
4mA
0
Offset
20mA
12mA
Gain
+16000
Digital
output
Current input
+32384
-384
Mode 6 of CR#2~ CR#5
+4mA ~ +20mA, Gain = 12mA (19,200), Offset = 4mA
(6,400).
Gain (CR#34 ~ CR#37)
The current input value when the digital output value =
16,000.
Offset (CR#28 ~ CR#31)
The current input value when the digital output value =
0.
Range of digital conversion 0 ~ 32,000
Max./Min. output range of
digital data
-384 ~ +32,384
Adjusting D/A Conversion Curve of CH5 ~ CH6
You can adjust the conversion curves according to the application requirements by changing
the Offset value (CR#32 ~ CR#33) and Gain value (CR#38 ~ CR#39).
Gain: The voltage (current) output value corresponding to digital value 16,000.
Offset: The voltage (current) output value corresponding to digital value 0.
z
For voltage output Mode 0: 0.3125mV = 20V/64,000
Equation
( )
(
)
⎟
⎠
⎞
⎜
⎝
⎛
×
⎥⎦
⎤
⎢⎣
⎡
+
−
×
=
32000
)
(
10
16000
V
Offset
Offset
Gain
X
V
Y
Y= Voltage output, X= Digital value
z
For current output Mode 1: 0.625
μ
A = 20mA/32,000.
Equation
( )
(
)
⎟
⎠
⎞
⎜
⎝
⎛
×
⎥⎦
⎤
⎢⎣
⎡
+
−
×
=
32000
)
(
20
16000
mA
Offset
Offset
Gain
X
mA
Y
Y= Current output, X= Digital value
z
For current output Mode 2: 0.5
μ
A = 16mA/32,000
Adopt the equation of current output Mode 1, substitute Gain for 19,200(12mA) and
Offset for 6,400(4mA)
Equation:
( )
(
)
⎟
⎠
⎞
⎜
⎝
⎛
×
⎥⎦
⎤
⎢⎣
⎡
+
−
×
=
32000
)
(
20
6400
16000
6400
19200
mA
X
mA
Y