E L C O p e r a t i o n M a n u a l
F o r m o r e i nf o r m a t i o n v i sit :
w w w. e a t o n . c o m
MN05003006E
1-118
C R # 8 , 9 , 1 0 , 11 :
CH1 ~ CH4 number of samples
1. The number of samples of the input signals for CH1 ~ CH4, used for the average input
values.
2. Allowable range: K1 ~ K100. Default = K10. If the value exceeds K100, the value will be
set to K100; if the value is less than K1, the value will be set to K1
C R # 1 2 , 1 3 , 1 4 , 1 5 :
Average input values at CH1 ~ CH4
The average value of the signals at CH1 ~ CH4 is calculated based on the number of
samples parameter set in CR#8 ~ CR#11. For example, if the value in CR#8 ~ CR#11 is K20,
the content in CR#12 ~ CR#15 will be the average from the most recent 20 signals in CH1 ~
CH4.
C R # 1 6 , 1 7 :
The output values for CH5 ~ CH6
Output value for CH5 ~ CH6: K-32,000 ~ K32,000. Default = K0.
C R # 2 0 , 2 1 , 2 2 , 2 3 :
Present input value at CH1 ~ CH4
The present value of input signals at CH1 ~ CH4.
C R # 2 8 , 2 9 , 3 0 , 3 1 :
Adjusted Offset values for CH1 ~ CH4
1. Set the adjusted Offset value of CH1 ~ CH4, which represents the voltage (current) input
value corresponds to digital value 0.
2. Default setting = K0.
C R # 3 2 , 3 3 :
Adjusted Offset values for CH5 ~ CH6
1. Set the adjusted Offset values for CH5 ~ CH6, which represent the voltage (current)
output value corresponds to digital value 0
2. Default setting = K0.
C R # 3 4 , 3 5 , 3 6 , 3 7 :
Adjusted Gain values for CH1 ~ CH4
1.
Set the adjusted Gain values for CH1 ~ CH4, which represent the voltage
(current) input value corresponds to digital value 16,000.
2.
Default
setting = K16,000.