3. AIAO Units
MN05003006E F or more information visit:
w w w. e a t o n . c o m
1-165
z
Mode 7: 1
SCALE
= 80mV/8000=0.01 mV
Equation:
⎟⎟
⎠
⎞
⎜⎜
⎝
⎛
+
=
Offset
V
V
X
Y
)
m
(
01
.
0
)
m
(
Y=Digital output, X= voltage input
C R # 4 0 :
Function: Prohibited configuration changes, Default = H’0000
Description
bit0
b0=0, CH1 changing allowed; b0=1, CH1 changing prohibited
bit1
b1=0, CH2 changing allowed; b1=1, CH2 changing prohibited
bit2
b2=0, CH3 changing allowed; b2=1, CH3 changing prohibited
bit3
b3=0, CH4 changing allowed; b3=1, CH4 changing prohibited
bit4 ~ bit15
Reserved
Affected Parameters
CR#2 ~ CR#5
Input mode for CH1 ~ CH4
CR#8 ~ CR#11
Number of samples for CH1 ~ CH4
CR#28 ~ CR#31
Offset settings for CH1 ~ CH4
CR#42
Returning to default settings
CR#100
Function: Enable/Disable limit detection
CR#102~CR#105
Configured value for CH1~CH4 upper limit
CR#108~CR#111
Configured value for CH1~CH4 lower limit
CR#120~CR#196 PID
settings
C R # 4 1 :
Function: Save all configuration values. Default=H’0000
Save all the configuration values to the internal flash memory. When saving is complete,
CR#41 will be set to H’FFFF.
Set value
Function
H0 No
action
HFFFF Saving
complete
H5678 Saving
enabled.
Note: Default setting = H0. When the value = H’5678, saving is enabled, and CR#41 will be
set to H’FFFF when complete.