E L C O p e r a t i o n M a n u a l
F o r m o r e i nf o r m a t i o n v i sit :
w w w. e a t o n . c o m
MN05003006E
1-112
Digital/Analog (D/A)
Voltage output
Current output
Mode 2 (H’0002): (+4mA ~ +20 mA)
20m A
+3 2,000
0
Offset
4m A
+1 6,000
12m A
C urren t
outpu t
D igita inpu t
l
Gai n
+3 2,767
-6,40 0
Mode -1 (H’FFFF): Channel
unavailable. The channel is
disabled. Output voltage = 0; output
current = 0.
Operation/storage
1. Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), pollution degree
2
2. Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity)
Vibration/shock
immunity
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc) / IEC61131-2 &
IEC 68-2-27 (TEST Ea)
Max. rated power
consumption
24V DC (20.4 ~ 28.8V DC) (-15% ~ +20%), 2.5W, supplied by external power
source
Weight 213g
3.2.3.4 Product Profile and Outline
70
62
106
98
78
90
61.5
11
0
EL CM -A N0 6A AN N
4 A I/2 A O
Direct mounting
hole
Model Name
Terminal No.
I/O module
connection port
Terminal No.
Power / A
D / Error indicators
←→
Removable I/O terminal
I/O module
connection port
I/O module clip
Mounting slot
(35mm)
Units: mm
3.2.3.5 Installation and Wiring
Installation of the DIN rail
1.
The ELC may be secured to a cabinet by using 35mm in height and 7.5mm in
depth DIN rail. When mounting the ELC to 35mm DIN rail, be sure to use the
retaining clip to stop any side-to-side movement of the ELC and reduce the
chance of wires coming loose. The retaining clip is at the bottom of the ELC. To
secure the ELC to DIN rail, pull down the clip, place it onto the rail and push it up
to lock it in place. To remove the ELC, pull the retaining clip down with a flat
screwdriver and remove the ELC from DIN rail.