3. AIAO Units
MN05003006E F or more information visit:
w w w. e a t o n . c o m
1-119
C R # 3 8 , 3 9 :
Adjusted Gain values for CH5 ~ CH6
1. Set the adjusted Gain values for CH5 ~ CH6, which represent the voltage (current)
output values corresponds to digital value 16,000.
2. Default setting = K16,000.
C R # 4 0 :
Function: Prohibited configuration changes, Default = H’0000
Description
bit0
b0=0, CH1 changing allowed; b0=1, CH1 changing prohibited
bit1
b1=0, CH2 changing allowed; b1=1, CH2 changing prohibited
bit2
b2=0, CH3 changing allowed; b2=1, CH3 changing prohibited
bit3
b3=0, CH4 changing allowed; b3=1, CH4 changing prohibited
bit4
b4=0, CH5 changing allowed; b4=1, CH5 changing prohibited
bit5
b5=0, CH6 changing allowed; b5=1, CH6 changing prohibited
bit6 ~ bit15
Reserved
Affected Parameters
CR#2 ~ CR#5
Input mode setting at CH1 ~ CH4
CR#6 ~ CR#7
Output mode setting at CH5 ~ CH6
CR#8 ~ CR#11
Sampling range of CH1 ~ CH4
CR#28 ~ CR#33
Adjusted Offset value of CH1 ~ CH6
CR#34 ~ CR#39
Adjusted Gain value of CH1 ~ CH6
CR#42
Return to default setting
CR#100
Function: Enable/Disable limit detection
CR#102~CR#107
Set value of CH1~CH6 upper bound
CR#108~CR#113
Set value of CH1~CH6 lower bound
CR#114~CR#115
Output update time of CH5~ CH6
CR#118
LV output mode setting of Ch5 ~ Ch6
C R # 4 1 :
Function: Save all configuration values. Default=H’0000
Save all the configuration values to the internal flash memory. When saving is completed,
CR#41 will be set to H’FFFF.
Set value
Function
H0 No
action
HFFFF Saving
completed
H5678 Saving
enabled.
Note: Default setting = H0. When the CR#41 value = H’5678, saving will be enabled, and
CR#41 will be set to H’FFFF when saving is complete.