1 . M P U U n i ts
MN05003006E For more informat ion visit :
w w w. e a t o n . c o m
1-37
1.2.4.6 A/D and D/A External wiring
ELC-PA Series
A/D Signal IN
CH0
100K
250
-10V~+10V
V+
I+
COM
CH1
250
-20mA~+20mA
V+
I+
COM
*3
*2
AG
AG
Current input
Voltage input
Shielded*1
Shielded*1
100K
CH0
CH1
100K
100K
Note 1: Isolate analog input wires from power wiring.
Note 2: If input signal is current, place a jumper between the V+ and I+ terminals.
Note 3: If the noise interference from loaded input wiring terminal is significant, please
connect a capacitor with 0.1~0.47
μ
F 25V for noise filtering.
Warning: DO NOT wire to the non functional terminals
D/A Signal OUT
V+
I+
COM
CH0
-10V~+10V
*5
CH0
V+
I+
COM
CH1
-20mA~20mA
CH1
24+
24-
DC24V
DC/DC
+15V
-15V
AG
voltage output
current output
AC drive, recorder,
scale valve...
shielding cable *1
shielding cable *4
AC drive, recorder,
scale valve...
terminal of
power module
class 3 grounding
(100 or less)
converter
Note 1: Isolate analog output wires from power wiring.
Note 2: If the noise interference from loaded output wiring terminal is significant, connect a
capacitor with 0.1~0.47
μ
F 25V for noise filtering.
Note 3: Connect power module ground terminal and analog output module ground
terminal to a system earth ground.
Содержание ELCM Series
Страница 1: ......
Страница 107: ...ELC Operation Manual For more information visit www eaton com MN05003006E 2 20 MEMO...