3. AIAO Units
MN05003006E F or more information visit:
w w w. e a t o n . c o m
1-27
Unit: LSB.
2. The adjustable range of voltage: -4V ~ +20V (0
LSB
~ +4,000
LSB
).
3. The adjustable range of current: -8mA ~ +40mA (0
LSB
~ +4,000
LSB
).
4. Note that: GAIN value – OFFSET value = +400
LSB
~ +6,000
LSB
(voltage or current). When
GAIN – OFFSET is small, the resolution of output signal will be finer and variation on the
digital value will be greater. When GAIN – OFFSET is large, the resolution of output
signal will be granier and the variation on the digital value will be smaller.
C R # 3 0 :
Data register for storing all errors
CR#30 is the fault code register. Refer to the following chart.
Fault Description
Content
b15~b8
b7 b6 b5 b4 b3 b2 b1 b0
Power
Source
Abnormal
K1(H1)
0
0 0 0 0 0
0
1
Analog output Value Error
K2(H2)
0
0 0 0 0 0
1
0
Setting
Mode
Error
K4(H4)
0
0 0 0 0 1
0
0
Offset/Gain
Error
K8(H8)
0
0 0 0 1 0
0
0
Hardware
Malfunction
K16(H10)
0
0 0 1 0 0
0
0
Digital
Range
Error
K32(H20)
0
0 1 0 0 0
0
0
Average
Times
Setting
Error K64(H40)
0
1 0 0 0 0
0
0
Command Error
K128(H80)
Reserved
1
0 0 0 0 0
0
0
Note: Each fault code will have corresponding bit (b0~b7). Two or more faults may happen
at the same time. 0 means normal and 1 means a fault occurred.
C R # 3 1 :
RS-485 communication address setting
The settings for the RS-485 communication address. Range: 01 ~ 255. Default = K1. This
setting is only valid for RS-485 communication and will be invalid when connected to an ELC
controller.
C R # 3 2 :
Communication speed (baud rate) setting
The RS-485 communication settings. Data rates: 4,800, 9,600, 19,200, 38,400, 57,600 and
115,200bps (bits per second). Default = H’0002.
b0 = 1:
4,800 bps
b1 = 1:
9,600 bps (default)
b2 = 1:
19,200 bps
b3 = 1:
38,400 bps
b4 = 1:
57,600 bps
b5 = 1:
115,200 bps
b6 ~ b13:
Reserved
b14:
High/low bit exchange of CRC checksum (only valid in RTU mode)
b15:
Switch between ASCII/RTU mode. 0: ASCII (default); 1: RTU. ASCII data
Содержание ELCM Series
Страница 1: ......
Страница 107: ...ELC Operation Manual For more information visit www eaton com MN05003006E 2 20 MEMO...