Affected Parameters
CR#34 ~ CR#37
Adjusted Gain value of CH1 ~ CH4
CR#100
Function: Enable/Disable limit detection
CR#102~CR#105
Set value of CH1~CH4 upper bound
CR#108~CR#111
Set value of CH1~CH4 lower bound
CR#114~CR#117
Output update time of CH1 ~ CH4
CR#118
LV output mode setting
C R # 4 3 :
Error Status. Default=H’0000
CR#43: Error status value. See the table below:
Description
bit0 K1
(H’1)
Power supply
error
bit11 K2048 (H’0800)
Upper / lower
bound setting error
bit1 K2 (H’2)
Hardware error
bit12 K4096 (H’1000)
Set value changing
prohibited
bit2 K4
(H’4)
Upper / lower
bound error
bit13 K8192 (H’2000)
Communication
breakdown on next
module
bit9 K512(H’0200)
Mode setting error
Note: Each error is determined by the corresponding bit (b0 ~ b13) and there may be
more than 2 errors occurring at the same time. 0 = normal; 1 = error
C R # 1 0 0 :
Function: Enable/Disable limit detection
Description
bit0=1
Enable CH1 limit detection
bit1=1
Enable CH2 limit detection
bit2=1
Enable CH3 limit detection
bit3=1
Enable CH4 limit detection
bit4 ~ bit7
Reserved
bit8=1
Disable output when CH1 exceeds the limit
bit9=1
Disable output when CH2 exceeds the limit
bit10=1
Disable output when CH3 exceeds the limit
bit11=1
Disable output when CH4 exceeds the limit
bit12 ~ bit15
Reserved
C R # 1 0 1 :
Upper and lower limit status
Description
bit0=1
CH1 exceeds lower bound