3. AIAO Units
MN05003006E F or more information visit:
w w w. e a t o n . c o m
1-145
Y = digital output, X = measured input temperature
Mode 4:
Equation:
⎟⎟
⎠
⎞
⎜⎜
⎝
⎛
−
=
Offset
X
Y
)
Ohm
(
1
.
0
)
Ohm
(
Y = digital output, X = measured input impedance
C R # 4 0 :
Function: Set prohibit configuration changes, Default = H’0000
Description
bit0
b0=0, CH1 changing allowed; b0=1, CH1 changing prohibited
bit1
b1=0, CH2 changing allowed; b1=1, CH2 changing prohibited
bit2
b2=0, CH3 changing allowed; b2=1, CH3 changing prohibited
bit3
b3=0, CH4 changing allowed; b3=1, CH4 changing prohibited
bit4 ~ bit15
Reserved
Affected Parameters
CR#2 ~ CR#5
Input mode configuration for CH1 ~ CH4
CR#8 ~ CR#11
Sampling range for CH1 ~ CH4
CR#28 ~ CR#31
Offset settings for CH1 ~ CH4
CR#42
Returning to default settings
CR#100
Function: Enable/Disable limit detection
CR#102~CR#105 Setting
of
CH1~CH4 upper limit
CR#108~CR#111 Setting
of CH1~CH4 lower limit
CR#120~CR#196
PID relative settings
C R # 4 1 :
Function: Save all the configuration values. Default=H’0000
Save configuration settings. Save all the configuration values to the internal flash memory.
When saving is complete, CR#41 will be set to H’FFFF.
Set value
Function
H0 No
action
HFFFF Saving
complete
H5678 Saving
enabled.
Note: Default = H0. When the value = H’5678, saving will be enabled, and CR#41 will be set
to H’FFFF when saving is complete.