3. AIAO Units
MN05003006E F or more information visit:
w w w. e a t o n . c o m
1-25
ELC-AN04NANN
EXPLANATION
bit
CR
No
Param.
Comm.
Add.
Latched
Register Name
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
#18 H’4044 O R/W
To adj. OFFSET value
of CH1
#19 H’4045 O R/W
To adj. OFFSET value
of CH2
#20 H’4046 O R/W
To adj. OFFSET value
of CH3
#21 H’4047 O R/W
To adj. OFFSET value
of CH4
It is used to set the OFFSET value for CH1~CH4. The
range is K-2,000~K2,000. The factory setting is K0 and
unit is LSB.
#24 H’404A O R/W
To adj. GAIN value of
CH1
#25 H’404B O R/W
To adj. GAIN value of
CH2
#26 H’404C O R/W
To adj. GAIN value of
CH3
#27 H’404D O R/W
To adj. GAIN value of
CH4
It is used to set the GAIN value for CH~CH4. The range
is K-1,600~K8,000. The factory setting is K2,000 and unit
is LSB.
#30 H’4050 X
R Error status
Data register to save all error status. Please refer to fault
code chart for detail.
#31 H’4051 O R/W
Communication
address setting
Used to set the RS-485 communication address. The
range is from 01 to 255 and the factory setting is K1.
#32 H’4052 O R/W
Communication Baud
Rate setting
Used to set communication baud rate (4,800, 9,600,
19,200, 38,400, 57,600, 115,200bps). Communication
format: ASCII mode is 7 Bit, even parity, 1 stop bit (7 E 1).
Communication format of RTU mode is 8 Bit, even parity,
1 stop bit (8 E 1).
b0: 4,800 bps (bit/sec).
b1: 9,600 bps (bit/sec). (Factory setting)
b2: 19,200 bps (bit/sec).
b3: 38,400 bps (bit/sec).
b4: 57,600 bps (bit/sec).
b5: 115,200 bps (bit/sec).
b6~b13: reserved.
b14: exchange low and high byte of CRC check code
(RTU mode only)
b15: ASCII / RTU mode selection
Reserved
CH4 CH3 CH2 CH1
#33 H’4053 O R/W
Reset to factory Reset
Reset to factory
default settings and
inhibit modifying Gain
and Offset values
Factory setting H0000
Example for CH1:
1. When b0=0, user can set OFFSET and GAIN values
for CH1 (CR#18, CR#24). When b0=1, inhibit the user
from modifying OFFSET and GAIN values for CH1.
2. b1=0 (factory setting, latched), b1=1 (not latched).
3. When b2 is set to 1, all settings will reset to factory
default settings.will reset to factory settings.
#34 H’4054 O
R Software version
Software version in hexadecimal. For example: H’010A
represents 1.0A.
Содержание ELCM Series
Страница 1: ......
Страница 107: ...ELC Operation Manual For more information visit www eaton com MN05003006E 2 20 MEMO...