Analog/Digital (A/D)
Voltage input
Current input
Self-diagnosis
Upper and lower bound detection/channel
Mode 0: (-10V ~ +10V), Mode 1: (-6V ~ +10V)
+2, 000
+1, 000
-1,000
10V
-2,000
-6V
-10V
6V
5V
2V
0
GAIN
OFFSET
Digital output
Voltage input
Mode 1
Mode 0
A/D conversion curve
(Default: mode 0)
Mode 2: (-12mA ~ +20mA), Mode 3: (-20mA ~ +20mA)
+1, 000
-1,000
-12mA
-20mA
4mA
0
OFFSET
20mA
GAIN
Digital output
Mode 3
Mode 2
Current input
Digital/Analog (D/A)
Voltage output
Current output
Analog output channel
2 channels/module
Range of analog output 0 ~ 10V
0 ~ 20mA
Range of digital data
0 ~ 4,000
0 ~ 4,000
Resolution
12 bits (1
LSB
= 2.5 mV)
12 bits (1
LSB
= 5
μ
A)
Overall accuracy
±0.5% when in full scale (25°C, 77°F)
±1% when in full scale within the range 0 ~ 55°C, 32~131°F
Output impedance
0.5
Ω
or lower
Response time
3 ms × the number of channels
Max. output current
20mA (1K
Ω
~ 2M
Ω
) -
Tolerable load
impedance
-
0 ~ 500
Ω
Digital data format
13 significant bits out of 16 bits are available; in 2’s complement
Isolation
Isolation between inner circuit and analog output terminal. There is no
isolation between channels.