3. AIAO Units
MN05003006E F or more information visit:
w w w. e a t o n . c o m
1-127
Current input mode
z
Mode 4 (H’0004): (-20mA~ +20mA)
+32000
+16000
-16000
20mA
-32000
-20mA
10mA
0
Gain
Offset
Digital
output
Current input
+32384
-32384
Mode 4 of CR#2~ CR#5
-20mA ~ +20mA, Gain = 10mA (16,000), Offset = 0mA
(0).
Gain (CR#34 ~ CR#37)
The current input value corresponds to digital value
16,000.
Offset (CR#28 ~ CR#31)
The current input value corresponds to digital value 0.
Range of digital conversion
-32,000 ~ +32,000
Max./Min. output range of
digital data
-32,384 ~ +32,384
z
Mode 5 (H’0005): (0 ~ +20mA)
+32000
+16000
20mA
10mA
0
Gain
Offset
Digital
output
Current input
+32384
-384
Mode 5 of CR#2~ CR#5
0mA ~ +20mA, Gain = 10mA (16,000), Offset = 0mA
(0).
Gain (CR#34 ~ CR#37)
The current input value corresponds to digital value
16,000.
Offset (CR#28 ~ CR#31)
The current input value corresponds to digital value 0.
Range of digital conversion
0 ~ 32,000
Max./Min. output range of
digital data
-384 ~ +32,384