Chapter 8 Logic Instructions
8_
The value of In
The value of Out
In < MN
MN
MN
≤
In
≤
MX
In
MX < In
MX
The instruction allows input parameters
MN
,
In
and
MX
to connect the variables of different data
types. When
MN
,
In
and
MX
are the variables of different data types, the calculation is performed
with the data type which can contain the range of the values of
MN
,
In
and
MX
. For example, if the
data type of
MN
is INT and the data types of
In
and
MX
are DINT, the data type of
Out
is DINT.
The instruction allows the input parameters and the output parameter to connect the variables of
different data types. But the length of the data type of the output variable must contain the length of
the variables that the input parameters
In0
~
InN
connect. Otherwise, an error will occur during the
compiling of the software.
Precautions for Correct Use
The input variables are not allowed to omit. An error will occur during the compiling of the software if
the input variables are omitted. But the output variable is allowed to omit.
Programming Example
The data types of LIMIT_MN, LIMIT_In and LIMIT_MX are UINT, UINT and DINT and the data type
of Out1 is DINT. When LIMIT_EN is TRUE, the value of Out1 is 50 if the values of LIMIT_MN,
LIMIT_In and LIMIT_MX are 1, 50 and 100 as shown in the following table Variable 1. If the values
of LIMIT_MN, LIMIT_In and LIMIT_MX are 2, 200 and 100, the value of Out1 is 100 as shown in the
following table Variable 2. If the values of LIMIT_MN, LIMIT_In and LIMIT_MX are 50, 10 and 100,
the value of Out1 is 50 as shown in the following table Variable 3.
Variable 1
Variable name
Data type
Current value
LIMIT_EN
BOOL
TRUE
LIMIT_MN
UINT
1
LIMIT_In
UINT
50
LIMIT_MX
DINT
100
Out1
DINT
50
Variable 2
Variable name
Data type
Current value
LIMIT_EN
BOOL
TRUE
LIMIT_MN
UINT
2
LIMIT_In
UINT
200
LIMIT_MX
DINT
100
Out1
DINT
100
Variable 3
Variable name
Data type
Current value
LIMIT_EN
BOOL
TRUE
LIMIT_MN
UINT
50
LIMIT_In
UINT
10
LIMIT_MX
DINT
100
Out1
DINT
50
8-141
Содержание DVP15MC11T
Страница 9: ...Memo viii...
Страница 15: ...DVP15MC11T Operation Manual _2 MEMO 2 4...
Страница 71: ...DVP15MC11T Operation Manual _7 Memo 7 10...
Страница 81: ...DVP15MC11T Operation Manual _8 Timing Chart F_TRG_CLK F_TRG_Q 8 10...
Страница 158: ...Chapter 8 Logic Instructions 8_ The program 1 ASIN EN ENO In Out ASIN_EN ASIN_In Out1 8 87...
Страница 213: ...DVP15MC11T Operation Manual _8 The program 1 LIMIT EN ENO MN Out MX In LIMIT_EN LIMIT_MN LIMIT_MX LIMIT_In Out1 8 142...
Страница 216: ...Chapter 8 Logic Instructions 8_ The program 1 BAND EN ENO MN Out MX In BAND_EN BAND_MN BAND_MX BAND_In Out1 8 145...
Страница 249: ...DVP15MC11T Operation Manual _8 8 178...
Страница 285: ...DVP15MC11T Operation Manual _8 Memo 8 214...
Страница 286: ...9 Chapter 9 Introductions of Axis Parameters Table of Contents 9 1 Description of Axis Parameters 9 2 9 1...
Страница 323: ...DVP15MC11T Operation Manual 10 MEMO 10 34...
Страница 549: ...DVP15MC11T Operation Manual A MEMO A 16...
Страница 571: ...DVP15MC11T Operation Manual C Memo C 10...
Страница 572: ...D Appendix D Explanation of Homing Modes Table of Contents D 1 Explanation of Homing Modes D 2 D 1...