SiUS34-801A_b
Field Settings
VRVIII R-410A Heat Pump 60Hz
111
Detailed Setting Procedure of Low Noise Operation and Demand Control
1. Setting mode 1 (H1P off)
In setting mode 2, push the BS1 (MODE button) one time.
→
Setting mode 2
is entered and
H1P lights.
During the setting mode 1 is displayed, “In low noise operation” and “In demand control” are
displayed.
2. Setting mode 2 (H1P on)
In setting 1, push and hold the BS1 (MODE button) for more than 5 seconds.
→
Setting mode 2
is entered and H1P lights.
Push the BS2 (SET button) several times and match the LED display with the Setting No. you
want.
Push the BS3 (RETURN button) one time, and the present setting content is displayed.
→
Push the BS2 (SET button) several times and match the LED display with the setting content
(as shown below) you want.
Push the BS3 (RETURN button) two times.
→
Returns to .
Push the BS1 (MODE button) one time.
→
Returns to the setting mode 1 and turns H1P off.
: ON : OFF
9
: Blink
Setting
No.
Setting
contents
Setting No. indication
Setting No. indication
Setting
contents
Setting contents indication (Initial setting)
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
H1P H2P H3P H4P H5P H6P H7P
12
External low
noise /
Demand
setting
NO (Factory
setting)
9
YES
9
22
Night-time
low noise
setting
OFF
(Factory
setting)
Mode 1
9
Mode 2
9
Mode 3
9
9
25
External low
noise
setting
Mode 1
9
Mode 2
(Factory
setting)
9
Mode 3
9
26
Night-time
low noise
start setting
PM 8:00
9
PM 10:00
(Factory
setting)
9
PM 0:00
9
27
Night-time
low noise
end setting
AM 6:00
9
AM 7:00
9
AM 8:00
(Factory
setting)
9
29
Capacity
precedence
setting
Low noise
precedence
(Factory
setting)
9
Capacity
precedence
9
30
Demand
setting 1
60 % of
rated power
consumption
9
70 % of
rated power
consumption
(Factory
setting)
9
80 % of
rated power
consumption
9
32
Normal
demand
setting
OFF
(Factory
setting)
9
ON
9
Setting mode indication section
Setting No. indication section
Set contents indication section
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...