SiUS34-801A_b
Operation Flow Chart
Indoor Unit
285
3. Operation Flow Chart
Start
Heating Operation
Fan Operation
Cooling Operation
Turn ON
power supply
Cooling Operation
LED in remote
controller turns ON
Drain
pump kit
Aux. electric
heater
Detect louver lock
( )
Run or Stop?
RUN indicating lamp: OFF
RUN indicating lamp: Blink
Malfunction code: Displayed
RUN indicating lamp: OFF
Malfunction mode display: Reset
Is
Restart prevention
operation in progress?
(5 min.)
Is
freeze prevention
operation in progress?
Is
test run
in progress?
Thermostat status
Fan or Temp.
control?
Cooling or
Heating?
Swing flap
Dew
prevention condition?
Swing flap
Set wind direction
Dew prevention position
Cassette type: P1
Ceiling suspended type: P0
Microcomputer dry
ON/OFF
Microcomputer dry display:
Reset
Microcomputer dry operation
Fan:
Operating with set air flow rate
A
A
A
Stop
Run
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
ON
OFF
No
No
No
Cyclic operation with
RUN/STOP pushbutton
*1
Fan
Temp. control
Heating
Cooling
*2 Fan : Stop
Louver : Stop
*3
*6
*5
*4
(Option)
(Option)
(Option)
(Option)
(Option)
(Option)
OFF
ON
MF
MF
: OFF
MP
Drain pump kit
: OFF after 5-min.
residual operation
MP
Drain pump kit
: OFF after 5-min.
residual operation
MP
Drain pump kit
:ON
MP
Drain pump kit
: ON
MP
: Closed
20E
Electronic expansion valve
: Capacity control
20E
Electronic expansion valve
: Closed
20E
MA
: OFF
52H
Aux. electric
heater
: OFF
52H
Humidifier : OFF
Mu
Humidifier : OFF
Mu
OFF
ON
a
b
Set temperature
Suction air temperature
a=b=1
(a=b=0.5 is only available for the FXCQ, FXFQ, FXHQ, and FXKQ series.)
20E
Initialize electronic
expansion valve
The previous settings of air
flow rate, wind direction, and
temperature are displayed.
Is the
safety device
activated?
Is the RUN
indicating lamp
blinking?
Press the RESET
RUN/STOP
pushbutton.
Electronic
expansion valve
Thermostat-ON-
operation signal to
outdoor unit: Output
Thermostat-ON-
operation signal to
outdoor unit: Output
*1. If any malfunction occurs, the relevant malfunction code will be displayed according to the malfunction
code display of the remote controller.
*2. When the aux. electric heater turns ON, the fan will stop after it conducts residual operation for 1 min.
*3. When the drain pump kit turns ON, the drain pump kit will stop after it conducts residual operation for a
period of 5 min.
*4. If the evaporator inlet temperature is kept at not more than 23
°
F for a period of cumulative 10 min. or
not more than 30.2
°
F for a cumulative period of 40 min., frost prevention operation will be conducted. If
the evaporator inlet temperature is kept at not less than 44.6
°
F for a consecutive period of 10 min., the
frost prevention operation will be reset.
*5. Thermostat status
*6. The FXCQ, FXFQ, FXKQ, and FXSQ series have the drain pump as standard equipment.
RUN indicating lamp: ON
Air flow rate display: Displayed
Wind direction display: Displayed
Temp. setting display: Displayed
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...