SiUS34-801A_b
Control of Electronic Expansion Valve
Indoor Unit
293
6. Control of Electronic Expansion Valve
Electronic expansion valves in indoor units conduct superheated degree control in cooling
operation and subcooled degree control in heating operation. If the indoor units receive any control
command such as a protection control command or a special control command from the outdoor
unit, the units will give priority to the control command.
• Superheated degree control in cooling operation
This function is used to adjust the opening of the electronic expansion valve so that superheated
degree (SH), which is calculated from the detection temperature (Tg) of the gas pipe thermistor
(R3T) and the detection temperature (T1) of the liquid temperature thermistor (R2T) of the indoor
unit, will come close to a target superheated degree (SHS).
At that time, correction to the superheated degree is made according to the differences (
Δ
T)
between set temperature and suction air thermistor temperature.
• Normally 41°F.
• As
Δ
T (Remote controller set temp. - return air temp.) becomes larger, SHS becomes
lower.
• As
Δ
T (Remote controller set temp. - return air temp.) becomes smaller, SHS becomes
higher.
• Subcooled degree control in heating operation
This function is used to adjust the opening of the electronic expansion valve so that the high-
pressure equivalent saturated temperature (Tc), which is converted from the detected pressure of
the high pressure sensor in the outdoor unit, and the subcooled degree (SC), which is calculated
from the detected temperature (T1) of the liquid temperature thermistor (R2T) in the indoor unit, will
come close to the target subcooled degree (SCS).
At that time, corrections to the subcooled degree are made according to differences (
Δ
T) between
set temperature and suction air thermistor temperatures.
• Normally 41°F.
• As
Δ
T (Remote controller set temp. - return temp.) becomes larger, SCS becomes lower.
• As
Δ
T (Remote controller set temp. - return temp.) becomes lower, SCS becomes larger.
SH = Tg - T1
SH: Evaporator outlet superheated degree (°F)
Tg: Indoor unit gas pipe temperature (R3T)
T1: Indoor unit liquid pipe temperature (R2T)
SHS (Target SH value)
SHS: Target superheated degree
SC = Tc - T1
SC: Condenser outlet subcooled degree (°F)
Tc: High pressure equivalent saturated temperature
detected by the high pressure sensor (S1NPH)
T1: Indoor unit liquid pipe temperature (R2T)
SCS (Target SC value)
SCS: Target subcooled
degree
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...