SiUS34-801A_b
Troubleshooting (OP: Unified ON/OFF Controller)
Troubleshooting
469
[Check 12] Check for shortage of refrigerant.
In case of VRV Systems, the only way to judge as the shortage of refrigerant is with operating
conditions due to the relationship to pressure control and electronic expansion valve control.
As information for making a judgment, refer to information provided below.
Diagnosis of shortage of refrigerant
1. The superheated degree of suction gas rises. Consequently, the compressor discharge gas
temperature becomes higher.
2. The superheated degree of suction gas rises. Consequently, the electronic expansion valve
opens.
3. Low pressure drops to cause the unit not to demonstrate cooling capacity (heating capacity).
Cooling
High pressure
Low pressure
Frequency
The opening degree of the indoor unit
motorized valve becomes larger.
Either of the motorized valves
becomes fully open.
Frequency comes to the minimum level.
Fan control is activated for HP
protection under cooling control
at low outdoor temperature,
i.e., the fan is hunting at HP.
HP drops with decrease
in compressor capacity.
If frequency comes to the
minimum level, LP
cannot be maintained.
LP rises as the opening
degree of the indoor unit
motorized valve becomes
larger. Frequency slightly
increases under the
capacity control.
To maintain LP,
frequency drops
due to the
capacity control.
Heating
High pressure
Low pressure
Frequency
The opening degree of the outdoor unit motorized valve becomes larger.
The outdoor unit motorized valve fully opens and frequency increases.
Discharge pipe or LP drooping control
(HP is maintained
at a constant level.)
Frequency comes to
the minimum level.
To maintain LP, frequency
drops due to the capacity
control.
Frequency drops
due to the drooping
control.
(Degree of refrigerant shortage)
Higher degree of shortage
Proper quantity
(LP is maintained
at a constant level.)
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...