Test Operation
SiUS34-801A_b
84
VRVIII R-410A Heat Pump 60Hz
4. If the
additional charging amount
was charged fully, close valve B and go to step 6.
If the
additional charging amount
was not charged fully, close valve B and go to step 5.
5. Perform the refrigerant charging following [Automatic refrigerant charging operation procedure]
as shown below. Charge the remaining refrigerant of the
additional charging amount
.
Note:
For performing the automatic refrigerant charging operation, the push buttons on the PC-board
(A1) of outside units are used. (See figure 29.)
Refrigerant is charged from the refrigerant charge port via valve A. (See figure 31.) For
operating the push button and opening or closing the valves, follow the procedure.
During Automatic refrigerant charging operation, the system will select charging mode (cooling
mode or heating mode) by the following temperature condition:
When charging in cooling mode, the system will stop operation when the required amount of
refrigerant is charged.
During charging in heating mode, a person must manually close valve A and stop operation.
Beforehand, check the remaining refrigerant that is needed to charge based on the
additional
charging amount
in step 2 and the charged amount in step 3.
The refrigerant will be charged about 66 lb in one hour at outdoor temp. 86°F DB (about 26 lb at
outdoor temp. 32°F DB).
During Automatic refrigerant charging operation, you can force the operation to stop by pushing
MODE button (BS1).
Measuring device
R-410A tank (with siphon)
Charge hose
Outside unit A
Indoor unit
Refrigerant charge port
Gas pipe shutoff valve
Liquid pipe shutoff valve
Valve A
Valve B
(
)
: Field pipings
: Refrigerant flow
: Shutoff valve
: Service port
Valve C
< RXYQ144PTJU Only >
fig. 30
Outdoor temp. : 32˚F DB ~ 109˚F DB
Indoor temp. :
50˚F DB ~ 90˚F DB
Less than above range
Cooling mode
Heating mode
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...