SiUS34-801A_b
Troubleshooting by Remote Controller
Troubleshooting
331
Outdoor Unit
L1
9
9
9
Malfunction of inverter PC board
L4
9
9
9
Malfunction of inverter radiating fin temperature rise
L5
9
9
9
DC output overcurrent of inverter compressor
L8
9
9
9
Inverter current abnormal
L9
9
9
9
Inverter start up error
LA
9
9
9
Malfunction of power unit
—
LC
9
9
9
Malfunction of transmission between inverter and
control PC board
P1
9
9
9
Inverter over-ripple protection
P4
9
9
9
Malfunction of inverter radiating fin temperature rise
sensor
PJ
9
9
9
Faulty field setting after replacing main PC board or
faulty combination of PC board
System
U0
8
7
9
Gas shortage alert
U1
9
9
9
Reverse phase / open phase
U2
9
9
9
Power supply insufficient or instantaneous failure
U3
9
9
9
Check operation is not completed.
U4
9
9
9
Malfunction of transmission between indoor and
outdoor units
U5
9
9
9
Malfunction of transmission between remote controller
and indoor unit
U5
7
8
7
Failure of remote controller PC board or setting during
control by remote controller
U7
9
9
9
Malfunction of transmission between outdoor units
421
U8
9
9
7
Malfunction of transmission between main and sub
remote controllers (malfunction of sub remote controller)
U9
9
9
9
Malfunction of transmission between indoor unit and
outdoor unit in the same system
UA
9
9
9
Improper combination of indoor and outdoor units,
indoor units and remote controller
UC
8
8
8
Address duplication of central remote controller
UE
9
9
9
Malfunction of transmission between central remote
controller and indoor unit
UF
9
9
9
Refrigerant system not set, incompatible wiring / piping
UH
9
9
9
Malfunction of system, refrigerant system address
undefined
Central
Remote
Controller
and
Schedule
Timer
M1
8
or
7
9
9
Central remote controller PC board defect
Schedule timer PC board defect
M8
8
or
7
9
9
Malfunction of transmission between optional
controllers for centralized control
MA
8
or
7
9
9
Improper combination of optional controllers for
centralized control
453
MC
8
or
7
9
9
Address duplication, improper setting
Heat
Reclaim
Ventilation
64
8
7
9
Indoor unit’s air thermistor error
—
65
8
7
9
Outside air thermistor error
—
6A
8
7
9
Damper system alarm
—
6A
9
9
9
Damper thermistor error
—
6F
8
7
9
Malfunction of simple remote controller
—
6H
8
7
9
Malfunction of door switch or connector
—
94
9
9
9
Internal transmission error
—
8
: ON
7
: OFF
9
: Blink
Malfunction
code
Operation
lamp
Inspection
display
Unit No.
Malfunction contents
Page
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...