Basic Control
SiUS34-801A_b
194
VRVIII R-410A Heat Recovery 60Hz
function is used to exert PI control on the electronic expansion valve (Y1E or Y3E) so that the
evaporator outlet superheated degree (SH) will become constant.
Subcooling electronic expansion valve EVT control
In order to make the maximum use of the subcool heat exchanger, this function is used to exert PI
control on the electronic expansion valve (Y2E, Y5E or Y3E) so that the evaporator-side gas pipe
superheated degree (SH) will become constant.
Refrigerant charge electronic expansion valve EVJ control
While in automatic refrigerant charge mode, this function is used to exert PI control on the opening
degree of the electronic expansion valve (Y2E or Y4E) in response to outdoor temperature and
close the valve after the completion of refrigerant charge.
For normal operation, fully open this electronic expansion valve.
6.4
Step Control of Outdoor Unit Fans
Used to control the revolutions of outdoor unit fans in the steps listed in table below, according to condition changes.
*
Figures listed above are all those controlled while in standard mode, which vary when the system is set to high static
pressure or capacity precedence mode.
6.5
Outdoor Unit Fan Control in Cooling Operation
While in cooling operation, if the outdoor temperature is low, this mode provides high-pressure
control using the outdoor unit fan to retain appropriate liquid pressure, thus ensuring refrigerant
SH = Tg - Te
SH : Evaporator outlet superheated degree (°F)
Tg : Suction pipe temperature (°F) detected by
the heat exchanger gas pipe thermistor
R2T.
Te : Low pressure equivalent saturated
temperature (°F)
SH = Tsh - Te
SH: Evaporator outlet superheated degree (°F)
Tsh:Suction pipe temperature (°F) detected by
the subcool heat exchanger outlet
thermistor R5T
Te: Low pressure equivalent saturated
temperature (°F)
STEP No.
Fan revolutions (rpm)
Single type
Multiple type
REYQ72P
REYQ96P
REYQ120P
REYQ144PTJU
REMQ72P
REMQ96P
REMQ120P
0
0
0
0
0
0
0
0
1
285/255
285/255
285/255
285/255
350
350
350
2
315/285
315/285
315/285
360/315
370
370
370
3
360/330
360/330
360/330
395/365
400
400
400
4
430/400
430/400
430/400
480/440
450
450
450
5
590/560
590/560
590/560
560/530
540
560
560
6
690/660
690/660
690/660
760/730
610
680
680
7
820/790
820/790
820/790
960/930
680
710
710
8
920/890
920/890
951/931
1155/1125
710
750
775
9
920/890
920/890
1020/990
1200/1170
796
821
870
Fan1/Fan2
Fan1/Fan2
Fan1/Fan2
Fan1/Fan2
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...