Symptom-based Troubleshooting
SiUS34-801A_b
318
Troubleshooting
1. Symptom-based Troubleshooting
Symptom
Probable Cause
Countermeasure
1
System does not start operation at all.
Blowout of fuse(s)
Turn Off the power supply and then
replace the fuse(s).
Cutout of breaker(s)
• If the knob of any breaker is in its
OFF position, turn ON the power
supply.
• If the knob of any circuit breaker
is in its tripped position, do not
turn ON the power supply.
Power failure
After the power failure is reset,
restart the system.
2
System starts operation but makes an immediate
stop.
Blocked air inlet or outlet of indoor
or outdoor unit
Remove obstacle(s).
Clogged air filter(s)
Clean the air filter(s).
3
System does not cool or heat air well.
Blocked air inlet or outlet of indoor
or outdoor unit
Remove obstacle(s).
Clogged air filter(s)
Clean the air filter(s).
Enclosed outdoor unit(s)
Remove the enclosure.
Improper set temperature
Set the temperature to a proper
degree.
Airflow rate set to
LOW
Set it to a proper airflow rate.
Improper direction of air diffusion
Set it to a proper direction.
Open window(s) or door(s)
Shut it tightly.
[In cooling] Direct sunlight received
Hang curtains or shades on
windows.
[In cooling] Too many persons staying in a
room
[In cooling] Too many heat sources (e.g. OA
equipment) located in a room
4
System does not
operate.
The system stops and
immediately restarts
operation.
If the
OPERATION
lamp on the
remote controller turns
ON
, the
system will be normal. These
symptoms indicate that the system
is controlled so as not to put
unreasonable loads on the system.
Normal operation. The system will
automatically start operation after a
lapse of five minutes.
Pressing the
TEMP ADJUST
button immediately resets the
system.
The remote controller displays
UNDER CENTRALIZED
CONTROL
, which blinks for a
period of several seconds
when the
OPERATION
button
is depressed.
The system is controlled with
centralized controller. Blinking
display indicates that the system
cannot be operated using the
remote controller.
Operate the system using the
COOL/HEAT centralized remote
controller.
The system stops immediately
after turning ON the power
supply.
The system is in preparation mode
of micro computer operation.
Wait for a period of approximately
one minute.
5
System makes
intermittent
stops.
The remote controller displays
malfunction codes [
U4
] and
[
U5
], and the system stops but
restarts after a lapse of
several minutes.
The system stops due to an
interruption in communication
between units caused by electrical
noises coming from equipment
other than air conditioners.
Remove causes of electrical noises.
If these causes are removed, the
system will automatically restart
operation.
ON
OFF
Knob
Tripped
Circuit breaker
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...