Troubleshooting by Indication on the Remote Controller
SiUS34-801A_b
416
Troubleshooting
Troubleshooting
Replace the compressor.
Replace the fan motor.
Replace the fan driver.
Replace the inverter PC board.
Observe the conditions of the
PC board.
In the case of a serious failure, a
compressor failure may cause
the failure of the PC board. Even
if the PC board is replaced, it
may cause failure again.
To avoid that, recheck the
compressor for ground and for
any broken wires. Furthermore,
even after the completion of PC
board replacement, check the
compressor.
Replace the fan driver PC board.
Observe the conditions of the
PC board.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Power ON
Power OFF
On-site causes.
Make proper wire connections
without open phase, erroneous
connections, or erroneous order of
phases.
On-site causes
Correct the unbalanced loads to
eliminate the unbalanced state.
Unbalanced voltage will cause
extremely unbalanced current,
thus impairing the service life of or
resulting in the malfunction of the
equipment.
NO
NO
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
Check for
power supply voltage.
Voltage between phases:
380 to 415V Phase
voltage: 220
to 240V
Unbalanced
power supply? (Not more
than 2%: Phase voltage of not
more than approx.
5V)
For 230V units:
(1) Does the power supply
voltage fall in the range of
230V±10%?
(2) Is there any open phase
or erroneous wiring in the
power supply line?
(3) Is an imbalance in power
supply voltage not more
than 6V?
The
insulation resistance is
low (i.e., not more than
100k
Ω
.)
The
insulation resistance is
low (i.e., not more than
1M
Ω
.)
Has the
power transistor got
faulty?
Has the
power transistor got
faulty?
Disconnect the cable from the
compressor, and then check
the compressor for the
insulation resistance.
Disconnect the cable from the
fan, and then check the fan
motor for the insulation
resistance.
Check the inverter power
transistor.
Check the fan driver power
transistor.
A
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...