Troubleshooting by Indication on the Remote Controller
SiUS34-801A_b
392
Troubleshooting
Troubleshooting
*1. List of Inverter PC boards
Model
Name
Electric symbol
RXYQ72, 96, 120PYDN, PTJU
REMQ72, 96, 120PYDN, PTJU
Compressor inverter PC board
A4P
Fan inverter PC board
A5P
REYQ72, 96, 120PYDN
REYQ72, 96, 120PTJU
Compressor inverter PC board
A5P
Fan inverter PC board
A6P, A7P
REYQ144PTJU
Compressor inverter PC board
A4P
RXYQ144PTJU
Fan inverter PC board
A5P
Do the
lead wires have any
disconnection, broken wire,
short circuit, or ground
fault?
Check 4
Check if the power
transistor is
normal.
YES
Check if
insulation resistance of
the compressor is 100k
Ω
and above.
NO
YES
Check 4
Check if the power
transistor of the fan
driver is normal.
NO
NO
YES
YES
NO
Replace the lead wires.
Replace the compressor and
compressor inverter PC board
(A2P) at the same time.
Replace the inverter PC board
(A2P).
Replace the compressor inverter
PC board (A2P) and fan inverter
PC board (A5P).
Replace the inverter PC board
(A2P).
Does the
power supply normally
come back ON?
Is the
single system applied
to the outdoor
unit?
YES
NO
It is supposed that the malfunction
results from external causes other
than failures (e.g. exogenous
noises or thunder).
YES
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
∗
∗
∗
Check 4
: Referring to the information on P463.
Turn OFF the power supply
once, and then check the
compressor lead wires.
Turn ON the power supply
again.
While in monitor mode, check
whether the system is right-
hand (control PC board 1) or
left-hand (control PC board 3).
While in monitor mode,
check the outdoor unit
concerned.
Single system
Multi system
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...