SiUS34-801A
Appendix 529
9. Example of Connection
Heat Pump
Example of connection
(Connection of 8 indoor units)
(*1) " " Indicate the Outside unit multi
connection piping kit.
(*2) In case of multi outdoor system, re-read
"outside unit" to "the first Outside unit
multi connection piping kit" as seen from
the indoor unit.
Branch with REFNET joint
Branch with REFNET joint and header
Branch with REFNET header
Single
outside
system
Multi
outside
system
Outside unit
Outside unit
Outside unit
Outside unit
Outside unit
REFNET joint (A~G)
REFNET joint (A~G)
Indoor unit ( 1 ~ 8 )
REFNET joint (A~G)
REFNET header
REFNET header
First outside unit multi connection piping kit
REFNET joint (A~G)
REFNET header
REFNET header
Maximum
allowable
length
Allowable
height
difference
Allowable length after the branch
Between outside unit (*2)
and indoor unit
Between first outside unit multi
connection piping kit and outside unit
(in case of multi system)
Between outside and indoor units
Between indoor and indoor units
Between outside and outside units
Actual pipe
length
Equivalent
length
Actual and
Equivalent
pipe length
Actual pipe
length
Difference in height
Difference in height
Difference in height
Total extention length
Pipe length between outside unit (*2) and indoor unit
≤
540 ft
Example 8 : a + b + c + d + e + o
≤
540 ft
Example 6 : a + b + h
≤
540 ft, 8 : a + i + j
≤
540 ft
Example 8 : a + i
≤
540 ft
Equivalent pipe length between outside unit (*2) and indoor unit
≤
620 ft (Note 1)
(Assume eqivalent pipe length of REFNET joint to be 1.6 ft, that of REFNET header to be 3.3 ft, for calculation purposes)
Total piping length from outside unit (*2) to all indoor unit
≤
3280 ft
Actual pipe length from first outside unit multi connection piping kit to outside unit
≤
33 ft
Equivalent pipe length from first outside unit multi connection piping kit to outside unit
≤
43 ft
Actual pipe length from first refrigerant branch kit (either REFNET joint or REFNET header) to indoor unit
≤
130 ft (Note 2)
Example 8 : b + c + d + e + o
≤
130 ft
Difference in height between outside unit and indoor unit (H1)
≤
164 ft (Max 130 ft if the outside unit is below)
Difference in height between adjacent indoor units (H2)
≤
49 ft
Difference in height between adjacent outside units (H3)
≤
16 ft
Outside unit
r
≤
33 ft
(Equivalent length
≤
43 ft)
t
≤
33 ft
(Equivalent length
≤
43 ft)
Example 6 : b + h
≤
130 ft, 8 : i + j
≤
130 ft
Example 8 : i
≤
130 ft
a
b
c
d
e
a
b
c
d
e
H1
H1
H1
H2
o
n
m
k
f
h
g
i
h
g
m
k
G
F
j
AB
C
D
E
H1
o
n
AB
C
D
E
12
34
567
8
H2
G
F
12
34
567
8
Indoor unit ( 1 ~ 8 )
Indoor unit ( 1 ~ 8 )
Indoor unit ( 1 ~ 8 )
Indoor unit ( 1 ~ 8 )
Indoor unit ( 1 ~ 8 )
a
a
i
i
cd
ef
g
h
A
A
B
H2
1
2
34
56
7
8
H3
r
t
H3
H3
r
t
a
b
cd
g
h
B
8
H2
r
t
a
12
3
4
5
6
7
b
c
j
b
e
f
d
c
b
e
fg
d
i
gh
H2
H1
H1
12
3
4
5
6
7
8
12
3
4
5
6
7
8
i
h
H2
r
t
ef
Outside unit
f
j
ij
k
k
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...