Troubleshooting by Remote Controller
SiUS34-801A_b
334
Troubleshooting
<Selection of setting item>
<Monitor mode>
<Confirmation of malfunction 1>
To enter the monitor mode, push the
MODE (BS1) button when in
“Setting mode 1”.
Push the SET (BS2) button and set
the LED display to a setting item.
Push the RETURN (BS3) button
once to display "First digit" of
malfunction code.
<Confirmation of malfunction 2>
Push the SET (BS2) button once to
display "Second digit" of malfunction
code.
Push the RETURN (BS3) button and
switches to the initial status of
“Monitor mode”.
∗
Push the MODE (BS1) button and
returns to “Setting mode 1”.
<Confirmation of malfunction 3>
Push the SET (BS2) button once to
display "malfunction location".
* Refer to Page 106, 254 for Monitor
mode.
* Refer to Page 106, 254 for Monitor
mode.
Detail
description
on next
page.
<Confirmation of malfunction 4>
Push the SET (BS2) button once to
display "master or slave 1 or slave 2"
and "malfunction location".
Malfunctions
Malfunction
code
Description of malfunction
Description of malfunction (PGF)
Remote
controller
INV PC board malfunction
Faulty IPM
L1
Current sensor failure confirmation 1
IGBT malfunction
Others
Faulty inverter setting
Rise in INV radiation fin temperature
Overheat of INV radiation fin temperature
L4
DC output overcurrent
Instantaneous overcurrent of INV
L5
Electronic thermal
Electronic thermal 1
L8
Electronic thermal 2
Loss of synchronization
Speed degradation after startup
Thunder detected
Stall prevention (time limit)
Stall prevention (increased current)
L9
Stall prevention (startup failure)
Abnormal starting waveform
Loss of synchronization
INV-Outdoor unit transmission malfunction INV transmission malfunction
LC
Open phase and unbalanced power supply
Unbalanced INV power supply voltage
P1
Switch box inside temperature sensor
malfunction
INV-box temperature thermistor
malfunction
P3
INV radiation fin temperature sensor malfunction
INV fin thermistor malfunction
P4
Faulty combination of INV and fan driver
Faulty combination of INV
PJ
Faulty combination of fan driver 1
Faulty combination of fan driver 2
Out of gas
Out-of-gas alarm
U0
Reversed phase
Reversed phase malfunction
U1
Abnormal power supply voltage
Insufficient INV voltage
U2
INV open phase (T phase)
Abnormal charge of capacitor of INV main circuit
Test run not carried out yet
Test run not carried out yet
U3
Alarm given when failing to measure the
amount of refrigerant during test run
Faulty transmission between indoor
and outdoor units
IN-OUT transmission malfunction
U4
System malfunction
Faulty transmission between outdoor
units
Sequential start ADP alarm
U7
Sequential start ADP malfunction
Multi transmission malfunction (Multi 1)
Multi transmission malfunction (Multi 2)
Faulty multi horsepower setting
Erroneous multi address
Excess multi connection
Multi system malfunction
Faulty transmission with other systems
Other system or other unit in the same system
U9
Faulty field setting
System transmission malfunction
UA
Excess indoor units connected
Faulty field setting
Erroneous refrigerant
Multi ID malfunction
TSS field setting alarm
CT address alarm
Faulty connection of BS units by heat
pump equipment
Faulty connection between multi heat
pump and heat recovery equipment
Faulty system line
Wrong wiring (auto address error)
UH
Faulty transmission with accessory
equipment
Multi level converter malfunction
UJ
Multi level converter alarm
Unmatched wiring/piping, no system settings Unmatched wiring/piping
UF
8
: ON
9
: Blink
1
: OFF
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...