Special Control
SiUS34-801A_b
60
VRVIII R-410A Heat Pump 60Hz
*
Pe_min and Pc_max indicate the minimum and maximum values in the system, respectively.
7.6
Standby
7.6.1 Restart Standby
Used to forcedly stop the compressor for a period of 2 minutes, in order to prevent the frequent ON/OFF of the compressor
and equalize the pressure within the refrigerant system.
Four way valve (High/low pressure
gas pipe switch)
20SB
Y8S
Y2S
OFF
OFF
Solenoid valve (Main bypass)
SVE
Y5S
Y6S
OFF
OFF
Y10S
Solenoid valve (Hot gas)
SVP
Y4S
Y5S
OFF
OFF
Solenoid valve (Refrigerant
regulator liquid pipe)
SVL
Y3S
Y4S
OFF
OFF
Solenoid valve (Refrigerant
regulator gas vent pipe)
SVG
Y1S
Y1S
OFF
OFF
Solenoid valve (Refrigerant
regulator exhaust pipe)
SVO
Y7S
Y7S
OFF
OFF
Solenoid valve (Refrigerant
regulator discharge pipe)
SVT
Y6S
Y8S
OFF
OFF
Ending conditions
•
3 min.
•
Pe_min<36.25psi
∗
•
Pc_max<453.85psi
∗
•
Master unit Tdi>230
°
F
•
Master unit Tp>284
°
F
Actuator
Symbol
Elect. symbol
Operation
RXYQ
144PTJU
For any model
other than that
shown on the left
Compressor 1
—
M1C
M1C
OFF
Compressor 2
—
M2C
M2C
OFF
Outdoor unit fan 1
—
M1F
M1F
Ta>86
°
F: STEP4
Ta
≤
86
°
F: OFF
Outdoor unit fan 2
M2F
—
Ta>86
°
F: STEP4
Ta
≤
86
°
F: OFF
Electronic expansion valve
(Main)
EVM
Y1E
Y1E
0 pls
Y3E
Electronic expansion valve
(Subcooling)
EVT
Y2E
Y3E
0 pls
Y5E
Electronic expansion valve
(Refrigerant charge)
EVJ
Y4E
Y2E
80 pls
Four-way valve (Heat
exchanger switch)
20SA
Y2S
Y3S
Holds
Y9S
Four-way valve (High/low
pressure gas pipe switch)
20SB
Y8S
Y2S
Holds
Solenoid valve (Main bypass)
SVE
Y5S
Y6S
OFF
Y10S
Solenoid valve (Hot gas)
SVP
Y4S
Y5S
OFF
Solenoid valve (Refrigerant
regulator liquid pipe)
SVL
Y3S
Y4S
OFF
Solenoid valve (Refrigerant
regulator gas vent pipe)
SVG
Y1S
Y1S
OFF
or
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...