SiUS34-801A_b
Thermostat Sensor in Remote Controller
Indoor Unit
289
4.1
Thermostat Control While in Normal Operation
VRV multi systems are set at factory to thermostat control mode using the remote controller. While
in normal thermostat differential control mode (i.e., factory set mode), the thermostat turns OFF
when the system reaches a temperature of -1.8°F from the set temperature while in cooling
operation or of +1.8°F from that while in heating operation.
While in a single remote controller group control, the return air sensor is only used from this
control. While in heating operation, cassette-mounted indoor units conduct the thermostat control
by a value compensated by -3.6°F for the value detected with the body thermostat. Through field
settings, the thermostat differential setting can be changed from 1.8°F to 0.9°F.
4.2
Thermostat Control in Dry Operation
While in dry operation, the thermostat control is conducted according to a return air temperature at
the time of starting the dry operation.
Assuming that the return air temperature at the time of starting the dry operation is Tro and the
return air temperature in operation is Tr:
While in dry operation mode, fans operate at L flow rate, stops for a period of six minutes while the
thermostat is OFF, and then return to operation at L flow rate. This control is used to prevent a rise
in indoor temperature while in thermostat OFF mode.
Cooling operation:
Heating operation:
Normal
operation
Thermostat OFF
Tr < Set temperature -1.8
ºF
Normal
operation
Thermostat OFF
Tr > Set tempe1.8
º
F
Tr: Temperature detected with the suction
air thermistor (R1T)
when Tro
≤
76.1
º
F:
when Tro > 76.1
º
F:
In dry operation
In dry operation
Tr < Tro -1.8
º
F
Tr < Tro -2.7
º
F
Thermostat OFF
Thermostat OFF
Tro: Suction air temperature at the
time of starting the dry operation
Tr: Temperature detected with the
suction air thermistor (R1T)
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...