SiUS34-801A_b
Test Operation
VRVIII R-410A Heat Pump 60Hz
85
[Automatic refrigerant charging operation procedure]
Note:
h
The marks of LED mean as follows.
h
: OFF
i
: ON
j
: Blinking
∗
: OFF, ON or Blinking
(1) Open the liquid pipe and gas pipe shutoff valves. (The valve A~C must be closed. See figure
31.)
(2)
•
Close the Electrical Components Box (1) lid and all front panel except on the Electrical
Components Box (1) side. (*1) Turn the power to the outdoor unit and all connected indoor
units. (*2)
•
After H2P stop blinking (about 12 minutes after turning on the power), check that H2P is OFF.
If H2P is ON, check the malfunction code in the remote controller of indoor unit and correct
the malfunction in accordance with [Remote controller display malfunction code] in chapter
11-2-2.
(3) Check the LED. Push the MODE button (BS1) once if the LED display is not as below:
Meas
u
ring
de
v
ice
R-410A tank (
w
ith siphon)
Charge hose
High side e
qu
alizer pipe sh
u
toff
v
al
v
e
V
al
v
e C
O
u
tside
u
nit A O
u
tside
u
nit B
V
al
v
e A
Indoor
u
nit
V
al
v
e B
Gas pipe sh
u
toff
v
al
v
e
Lo
w
side e
qu
alizer pipe sh
u
toff
v
al
v
e
Li
qu
id pipe sh
u
toff
v
al
v
e
Refrigerant charge port
V
al
v
e A
: Field pipings
: Refrigerant flo
w
w
hen charging
: Sh
u
toff
v
al
v
e
( : Ser
v
ice port)
The refrigerant
w
ill
b
e charged a
b
o
u
t 66 l
b
in one ho
u
r at o
u
tdoor temp.
8
6°FDB (26 l
b
at 32°FDB). (According to o
u
tdoor temp. or
the refrigerant amo
u
nt in the tank, the
charging rate may speed
u
p). If yo
u
need to
speed
u
p in case of m
u
lti system, connect
the refrigerant tanks to each o
u
tside
u
nit.
H1P H2P H3P H4P H5P H6P H7P
h
h
i
h
h
h
h
fig. 31
< RXYQ144PTJU Only >
Measuring device
R-410A tank (with siphon)
Charge hose
Outside unit A
Indoor unit
Refrigerant charge port
Gas pipe shutoff valve
Liquid pipe shutoff valve
Valve B
Valve A
(
)
: Field pipings
: Refrigerant flow when charging
: Shutoff valve
: Service port
Valve C
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...