SiUS34-801A_b
Field Settings
VRVIII R-410A Heat Pump 60Hz
117
<RXYQ144, 168, 192, 216, 240PYDN, RXYQ168, 192, 216, 240PTJU>
Cancel the disable-operation setting by each outdoor unit.
Make the following setting on the outdoor unit 1. If this setting is made on an outdoor unit other than
the outdoor unit 2, the setting will become invalid.
*It is possible to tell the outdoor units 1 and 2 according the LED displays shown below.
8
Cancel disabling the outdoor unit 1 from operating:
Set No. 38
Disable outdoor unit 1 operation
of
setting mode 2
to
OFF
.
8
Cancel disabling the outdoor unit 2 from operating:
Set No. 39
Disable-outdoor-unit-2 operation
of
setting mode 2
to
OFF
.
LED display (
8
: ON,
1
: OFF,
9
: Blink)
H1P-----------H7P H8P
Outdoor unit 1:
1181111 8
Outdoor unit 2:
1111111 9
LED display (
8
: ON,
1
: OFF,
9
: Blink)
(Step)
H1P-----------H7P
(1) Press and hold the
MODE
button (BS1)
for 5 sec. or more.
8111111
(2) Press the
SET
button (BS2) 38 times.
8811881
(3) Press the
RETURN
button (BS3) once.
8111191
(4) Press the
SET
button (BS2) once.
8111119
(Factory setting)
(5) Press the
RETURN
button (BS3) twice.
8111111
(6) Press the
MODE
button (BS1) once.
1181111
LED display (
8
: ON,
1
: OFF,
9
: Blink)
(Step)
H1P-----------H7P
(1) Press the
MODE
button (BS1) for 5
seconds or more.
8111111
(2) Press the
SET
button (BS2) 39 times.
8811888
(3) Press the
RETURN
button (BS3) once.
8111191
(4) Press the
SET
button (BS2) once.
8111119
(Factory setting)
(5) Press the
RETURN
button (BS3) twice.
8111111
(6) Press the
MODE
button (BS1) once.
1181111
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...