Field Setting
SiUS34-801A_b
302
Indoor Unit
12.1.4 Setting Contents and Code No. – VRV Indoor unit
Notes :
1. Settings are made simultaneously for the entire group, however, if you select the mode No.
inside parentheses, you can also set by each individual unit. Setting changes cannot be
checked except in the individual mode for those in parentheses.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so they
cannot be set individually. Setting changes also cannot be checked.
3. Marked
are factory set.
4. Do not make settings other than those described above. Nothing is displayed for functions the
indoor unit is not equipped with.
5. [88] may be displayed to indicate the remote controller is resetting when returning to the normal
mode.
6. If the setting mode to [Equipped] the heat reclaim ventilation fan conducts the fan residual
operation by linking to indoor unit.
VRV
system
indoor
unit
settings
Mode
No.
Note 2
Setting
Switch
No.
Setting Contents
Second Code No.(Note 3)
Details
No
01
02
03
04
10(20)
0
Filter contamination heavy/
light (Setting for display
time to clean air filter)
(Sets display time to clean
air filter to half when there
is heavy filter
contamination.)
Super long
life filter
Light
Approx.
10,000
hrs.
Heavy
Approx.
5,000
hrs.
—
—
(1)
Long-life filter
Approx.
2,500
hrs.
Approx.
1,250
hrs.
Standard
filter
Approx.
200
hrs.
Approx.
100
hrs.
1
Long-life filter type
Long-life filter
Super long-life filter
—
—
(2)
2
Thermostat sensor in remote controller
Remote
cont Body
thermostat
Only body
thermostat
Only remote
controller
thermostat
—
(3)
3
Display time to clean air filter calculation
(Set when filter sign is not to be displayed.)
Display
No display
—
—
(4)
12(22)
0
Optional accessories output selection (field
selection of output for adaptor for wiring)
Indoor unit
turned ON by
thermostat
—
Operation
output
Malfunction
output
(5)
1
ON/OFF input from outside (Set when ON/
OFF is to be controlled from outside.)
Forced OFF
ON/OFF control
External
protection
device input
—
(6)
2
Thermostat differential changeover
(Set when remote sensor is to be used.)
1.8°F
0.9°F
—
—
(7)
3
Air flow setting when heating thermostat is
OFF
LL
Set fan speed
—
—
(8)
4
Automatic mode differential (automatic
temperature differential setting for VRV
system heat recovery series cool/heat)
01:0
02:1
03:2
04:3
05:4
06:5
07:6
08:7
(9)
5
Power failure automatic reset
Not equipped
Equipped
—
—
(10)
6
Air flow setting when Cooling thermostat is
OFF
LL
Set fan speed
—
—
(11)
13(23)
0
Setting of normal air flow
N
H
S
—
(12)
1
Selection of air flow direction
(Set when a blocking pad kit has been
installed.)
F (4 directions)
T (3 directions)
W (2
directions)
—
(13)
3
Operation of downward flow flap: Yes/No
Equipped
Not equipped
—
—
(14)
4
Field set air flow position setting
Draft prevention
Standard
Ceiling
Soiling
prevention
—
(15)
5
Setting of static pressure selection
Standard
High static
pressure
—
—
(16)
15(25)
1
Thermostat OFF excess humidity
Not equipped
Equipped
—
—
(17)
2
Direct duct connection
(when the indoor unit and heat reclaim
ventilation unit are connected by duct
directly.)
∗
Note 6
Not equipped
Equipped
—
—
(18)
3
Drain pump humidifier interlock selection
Not equipped
Equipped
—
—
(19)
5
Field set selection for individual ventilation
setting by remote controller
Not equipped
Equipped
—
—
(20)
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...