SiUS34-801A_b
Other Control
VRVIII R-410A Heat Pump 60Hz
71
9. Other Control
9.1
Backup Operation
If any of the compressors malfunctions, disable the relevant corresponding compressor or outdoor
unit, and then conduct emergency operation only with operational compressors or outdoor units.
Emergency operation with remote controller reset
and
Emergency operation with outdoor
unit PC board setting
are available.
(1) Emergency operation with remote controller reset
[Operating method]
Reset the remote controller. Press the [
RUN/STOP
] button for 4 seconds or more.[Details of
operation]
Disable the defective outdoor unit from operating, and then only operate other outdoor units.
On systems with 1 outdoor unit, this emergency operation is not available.
(2) Emergency operation with outdoor unit PC board setting
[Setting method]
Make setting of the compressor,
the operation of which is to be disabled
, in field setting
mode (setting mode 2).
For detail of the setting method, refer to page 113.[Details of operation]
Disable the compressor with the
operation disable
setting made from operating and only
operate other compressors.
9.2
Demand Operation
In order to save the power consumption, the capacity of outdoor unit is saved with control forcibly
by using
Demand 1 Setting
or
Demand 2 Setting
.
To operate the unit with this mode, additional setting of
Continuous Demand Setting
or
external input by external control adapter is required.
9.3
Heating Operation Prohibition
Heating operation is prohibited above 75.2°F ambient temperature.
Operating method
Applicable model
(1) Emergency operation with
remote controller reset
(Auto backup operation)
(2) Emergency operation with
outdoor unit PC board setting
(Manual backup operation)
RXYQ72~120PYDN
RXYQ72~144PTJU
–
Backup operation by the
compressor
RXYQ144~240PYDN
RXYQ168~240PTJU
Backup operation by the
indoor unit
Backup operation by the
outdoor unit
Set item
Condition
Content
Demand 1
Mode 1
The compressor operates at approx. 60% or less of rating.
Mode 2
The compressor operates at approx. 70% or less of rating.
Mode 3
The compressor operates at approx. 80% or less of rating.
Demand 2
⎯
The compressor operates at approx. 40% or less of rating.
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...