SiUS34-801A_b
Field Settings
VRVIII R-410A Heat Pump 60Hz
113
12.1.7 Check Operation Detail
12.1.8 Emergency Operation
If any of the compressors malfunctions, disable the corresponding compressor or outdoor unit, and
then conduct emergency operation only with operational compressors or outdoor units.
There are two ways of conducting the Emergency operation :
N
with remote controller reset and
O=
by setting outdoor unit PC board.
N
Emergency operation with remote controller reset
On the multi outdoor unit system, if any of the outdoor unit line causes a malfunction (in this
case, the system will stop and the corresponding malfunction code will be displayed on the
indoor remote controller), disable only the corresponding outdoor unit from operating for a 8
hours using the indoor remote controller, and then conduct emergency operation with
operational outdoor units.
[Emergency operation method]
•
Reset the remote controller (i.e., press the RUN/STOP button on the remote controller for 4
seconds or more) when the outdoor unit stops because of malfunction state.
[Details of operation]
Unit stopping
Press the TEST button for 5 seconds.
10 sec to 10 minutes
LED display (H1P~H7P) (
8
:
ON
3
:
OFF
9
:
BLINK)
3383333
3933338
Pressure equalizing
Step 1
20 sec to 2 minutes
Stop valve check
Stop valve check
Wrong wiring check
Piping length check
5 minutes
3933383
Cooling start control
Step 2
3933388
3938338
3938383
Stop valve close check
Step 3
Pump down residual operation
Step 9
5 minutes
Standby for restarting
Completion
Step 10
•
Wrong wiring check
•
Correct Refrigerant charge check
•
Piping length check
Judgement function
Step4~8
CHECK OPERATION FUNCTION
(Press the MODE button BS1 once and set to SETTING MODE 1 (H1P: OFF))
•
Stop valve close check
3933833
3933838
3933883
Operating method
Applicable model
N
Emergency operation with
remote controller reset
(Auto backup operation)
O
Emergency operation with
outdoor unit PC board setting
(Manual backup operation)
RXYQ72 to 120PYDN, PTJU
RXYQ144PTJU
–
Backup operation by the
compressor
RXYQ144 to 240PYDN
RXYQ168 to 240 PTJU
Backup operation by the
indoor unit
Backup operation by the
outdoor unit
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...