SiUS34-801A_b
Test Operation
VRVIII R-410A Heat Pump 60Hz
89
[Remote controller displays malfunction code]
Note:
If any malfunction codes other than the above are displayed, check the service manual for how to
respond.
10.2.6 Onsite Settings
Note:
In the case of a multi system, all onsite settings should be made on the master unit. Settings made
on sub units are invalid.
The outside unit to which the indoor unit transmission wire is connected is the master unit, and all
other units are sub units.
Use the push button switches (BS1 through BS5) on the outside unit PC-board (A1P) to make the
necessary onsite settings.
See the [
Service Precautions
] label (upper) on the Electrical Componets Box lid for details on the
positions and operating method of the push button switches and on the onsite setting.
Make sure to record the setting on the accessory [
REQUEST FOR THE INDICATION
] label.
WARNING
Electric Shock Warning
Use an insulated rod to operate the push buttons via the inspection door of Electrical Componets
Box lid.
There is a risk of electric shock if you touch any live parts as operation must be performed with the
power on.
10.2.7 Test Run
10.2.7.1 Before test run
Make sure the following works are completed in accordance with the installation manual.
Piping work
Wiring work
Air tight test
Vacuum drying
Additional refrigerant charge
Check operation
Check that all work for the BS and indoor units is finished, and that it is safe to operate.
Malfunction code Installation error
Remedial action
E3, E4
F3, F6
UF
The shutoff valve of the outside unit is left closed.
Open the shutoff valve.
U1
The phases of the power to the outside unit is
reversed.
Exchange two of the three phases (L1, L2, L3) to make a proper
connection.
U1
U4
LC
No power is supplied to an outside, BS or indoor
unit (including phase interruption).
Make sure the power source wire is properly connected to the out-
side, BS or indoor unit and revise if necessary.
UF
There is conflict on the connection of transmission
wiring in the system.
Check if the refrigerant piping line and the transmission wiring are
consistent with each other.
E3
F6
UF
Refrigerant overcharge.
Recalculate the additional amount refrigerant from the piping length
and correct the refrigerant charge level by recovering any excessive
refrigerant with a refrigerant recovery machine.
E4
F3
Insufficient refrigerant.
• Check if the additional refrigerant charge has been finished cor-
rectly.
• Recalculate the additional amount
refrigerant from the piping length and add the adequate amount.
U7, U4
UF, UH
Field wiring is connected to
TO MULTI UNIT
(Q1,Q2)
terminal on the outside unit PC-board (A1P)
when the system is one outdoor system.
Remove the line from the
TO MULTI UNIT
(Q1, Q2)
terminal.
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...