SiUS34-801A_b
Troubleshooting (OP: Unified ON/OFF Controller)
Troubleshooting
461
[CHECK 4] Power Transistor Check
Perform the following procedures prior to check.
(1) Power Off.
(2) Remove all the wiring connected to the PC board where power transistors are mounted on.
[Preparation]
· Tester
∗
Preparing a tester in the analog system is recommended.
A tester in the digital system with diode check function will
be usable.
[Point of Measurement and Judgment Criteria]
· Measure the resistance value using a tester at each point of measurement below, 10 minutes later after power OFF.
To use analog tester:
Measurement in the resistance value mode in the range of
multiplying 1k
Ω
.
Point of Measurement
Judgment Criteria
Remarks
+
–
No.
15k
Ω
and
above
(including
)
2 ~ 15k
Ω
2 ~ 15k
Ω
Due to condenser charge
and so on, resistance
measurement may require
some time.
P2
P2
P2
U
V
W
N3
N3
N3
U
V
W
1
2
3
4
5
6
7
8
9
10
11
12
P2
P2
P2
U
V
W
U
V
W
N3
N3
N3
Point of Measurement
Judgment Criteria
Remarks
+
–
No.
0.3 ~ 0.7V
1.2V and over
1.2V and over
Due to condenser charge
and so on, resistance
measurement may require
some time.
Due to condenser charge
and so on, resistance
measurement may require
some time.
P2
P2
P2
U
V
W
N3
N3
N3
U
V
W
1
2
3
4
5
6
7
8
9
10
11
12
P2
P2
P2
U
V
W
U
V
W
N3
N3
N3
To use digital tester:
Measurement is executed in the diode check mode. ( )
[PC board and Circuit Diagram]
P3
U
V
W
N3
J1
J2
J3
P1
P1
P2
IGBT
X11A
U
V
W
L1
L2
L3
X10A
DM
K2
P3
N3
(V2895)
J1
J2
J3
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...