SiUS34-801A_b
Test Operation
VRVIII R-410A Heat Recovery 60Hz
237
Maximum concentration level
The maximum charge of refrigerant and the calculation of the maximum concentration of refrigerant
is directly related to the human-occupied space into which it could leak.
The unit of measurement of the concentration is lb/ft
3
(the weight in lb of the refrigerant gas in 1 ft
3
volume of the occupied space).
Compliance to the local applicable regulations and standards for the maximum allowable
concentration level is required.
1.direction of the refrigerant flow
2.room where refrigerant leak has occurred (outflow of all the refrigerant from the system)
Pay a special attention to the place, such as a basement, where refrigerant can stay, since
refrigerant is heavier than air.
Procedure for checking maximum concentration
Check the maximum concentration level in accordance with steps 1 to 4 below and take whatever
action is necessary to comply.
1. Calculate the amount of refrigerant (lb) charged to each system separately.
Note:
Where a single refrigerant facility is divided into 2 entirely independent refrigerant systems, use
the amount of refrigerant with which each separate system is charged.
2. Calculate the smallest room volume (ft
3
)
For the following cases, calculate the volume of (A), (B) as a single room or as the smallest
room.
A.
Where there are no smaller room divisions
B.
Where there is a room division but there is an opening between the rooms sufficiently large to
permit a free flow of air back and forth.
1.opening between rooms
2.partition
Where there is an opening without a door or where there are openings above and below the door
that are each equivalent in size to 0.15% or more of the floor area.
amount of refrigerant in a
single unit system (amount
of refrigerant with which the
system is charged before
leaving the factory)
+
additional charging amount
(amount of refrigerant added
locally in accordance with the
length or diameter of the
refrigerant piping)
=
total amount of
refrigerant (lb) in
the system
2
1
1
2
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...