SiUS34-801A_b
Protection Control
VRVIII R-410A Heat Pump 60Hz
67
8.3
Discharge Pipe Protection Control
This discharge pipe protection control is used to protect the compressor internal temperature
against a malfunction or transient increase of discharge pipe temperature.
[Contents]
The following control is performed for each compressor.
[INV compressor]
*1:
HTdi
represents a value obtained by correcting the discharge pipe temperature (Tdi) of INV
compressor with an outdoor temperature.
*2: For
INV
compressor steps, refer to information on page 45.
[STD compressor]
&
&
OR
• HTdi< 230°F
• A lapse of 20 sec.
• HTdi>239°F
• A lapse of 30 sec.
Matching of fre
qu
ency
• HTdi>266°F
• HTdi>24
8
°F contin
u
es
for a period of 90 sec.
OR
• HTdi>275°F
• HTdi>24
8
°F
contin
u
es for a period
Stop d
u
e to malf
u
nction
[
F3
] is displayed.)
Discharge pipe
temperat
u
re stand
b
y
occ
u
rs 3 times for a
period of 100 min.
I
NV
compressor (See *2):
1-step
u
p per 20 sec.
Restart stand
b
y: 10 min.
(
u
p to 2 times for a
period of 100 min.)
Compressor system (See *2):
Step 1
I
NV
compressor (See *2):
1-step per 30 sec.
OR
After a lapse of 10 min.
Normal operation
STD compressor stops
running.
HTds: Represents a value obtained by correcting
the discharge pipe temperature (Tds) of STD
compressor with an outdoor temperature.
• HTds>248˚F continues for a period
of consecutive 5 min. or more.
• HTds>275˚F
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...