Test Operation
SiUS34-801A_b
82
VRVIII R-410A Heat Pump 60Hz
10.2.5.2Procedure of Adding Refrigerant charging and check operation
WARNING
Electric Shock Warning
Make sure to close the Electrical Components Box lid before turning on the power.
Perform the setting on the PC-board (A1P) of the outside unit and check the LED display after
the power is on via the inspection door which is in the Electrical Components Box lid.
Use an insulated rod to operate the push buttons via the Electrical Components Box’s
inspection door.
There is a risk of electric shock if you touch any live parts, since this operation must be
performed with the power on.
Caution:
Make sure to use protection tools (protective groves and goggles) when charging the
refrigerant.
Due to a danger of liquid hammer, the refrigerant must not be charged over the allowable
maximum amount when charging the refrigerant.
Do not perform the refrigerant charging operation while working on the BS and indoor unit.
When opening the front panel, be cautious of the rotating fan. After the outside unit stops
operating, the fan may continue to rotate for a while.
Note:
If operation is performed within 12 minutes after the BS, indoor and outside units are turned on,
H2P will be lit on and the compressor will not operate.
Check the LED display indicate as shown below.
In order to ensure uniform refrigerant distribution, it may take up to around 10 minutes for the
compressor to start up after the unit starts operating. This is not a malfunction.
The refrigerant charge port is connected to the piping inside the unit.
Inspection door
Inspection door
P
u
sh
bu
tton (BS1
~
5)
fi
g
. 29
Lift the protr
u
ding part to open the inspection door.
LED (H1
~8
P)
ELECTRICAL COMPO
N
E
N
TS BOX(1)
ELECTRICAL COMPO
N
E
N
TS BOX(1) lid
(Only RXYQ144PTJU)
ELECTRICAL COMPO
N
E
N
TS BOX (2)
< RXYQ144PTJU Only >
(Only RXYQ144PTJU)
Do not open the
ELECTRICAL COMPO
N
E
N
TS
BOX(2) lid or that
inspection door.
ELECTRICAL COMPO
N
E
N
TS BOX(1)
ELECTRICAL COMPO
N
E
N
TS BOX lid
H1P H2P H3P H4P H5P H6P H7P
h
i
h
h
h
h
h
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...