SiBE37-701_B
Basic Control
Function
118
2.6
Heat Exchanger Control
While in heating or cool/heat simultaneous operation, ensure target condensing and
evaporating temperature by changing over the air heat exchange of outdoor unit to the
evaporator or the condenser in response to loads.
[Single system]
[Multi outdoor unit system]
Outdoor unit
Left side
Condenser
Right side
Condenser
GR < -20
GR > 25
Outdoor unit
Left side
Evaporator
Right side
Condenser
GR > 25
GR < -20
Outdoor unit
Left side
Evaporator
Right side
–
Outdoor unit
Left side
Evaporator
Right side
Evaporator
GR < -10
GR > 15
Note 1. "GR" is a numeric value
representing the current
balanced condition and
calculated from target
condensing temperature,
target evaporating
temperature, current
condensing temperature,
and current evaporating
temperature.
A1
A2
A3
A4
Outdoor unit
1
2
3
Condenser Condenser Condenser
GR < -10
GR > 15
Outdoor unit
1
2
3
Condenser Condenser Condenser
GR < -20
GR > 25
Outdoor unit
1
2
3
Condenser Condenser
–
GR < -10
GR > 15
Outdoor unit
1
2
3
Condenser Evaporator Evaporator
Note 1. "GR" is a numeric value representing the current balanced
condition and calculated from target condensing temperature,
target evaporating temperature, current condensing temperature,
and current evaporating temperature.
Note 2. On the system with two outdoor units, if there is no step for the
destination of transition, that step will be skipped.
B1
B2
B3
GR > 25
GR < -20
GR > 25
Outdoor unit
1
2
3
–
Evaporator
–
GR < -10
GR > 15
Outdoor unit
1
2
3
Evaporator Evaporator
–
GR < -10
GR > 15
Outdoor unit
1
2
3
Evaporator Evaporator Evaporator
Содержание REYQ8-48PY1B
Страница 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Страница 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Страница 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Страница 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...