SiBE37-701_B
Troubleshooting by Indication on the Remote Controller
Troubleshooting
310
3.32
“
J6
”
Outdoor Unit: Malfunction of Thermistor (R4T or
R12T) for Outdoor Unit Heat Exchanger
Remote
Controller
Display
J6
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the heat exchanger thermistor.
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the heat exchanger thermistor is detected.
Supposed
Causes
Defect of thermistor (R4T or R12T) for outdoor unit heat exchanger
Defect of outdoor unit PCB (A1P)
Defect of thermistor connection
Troubleshooting
∗
Refer to “Thermistor Resistance / Temperature Characteristics” table on P450.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Connector is
connected to X30A
of outdoor unit PCB
(A1P).
NO
Connect the connector and turn on
again.
Confirm which thermistor is
abnormal using outdoor unit
"monitor mode".
(Refer to P.255~P.256)
Resistance is normal
when measured after
disconnecting the
thermistor R4T or
R12T from the indoor
unit PCB. (1.8k
Ω
to
800k
Ω
)
YES
NO
YES
Replace the thermistor R4T or
R12T.
Replace the outdoor unit PCB
(A1P).
Содержание REYQ8-48PY1B
Страница 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Страница 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Страница 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Страница 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...