![Daikin REYQ8-48PY1B Скачать руководство пользователя страница 428](http://html.mh-extra.com/html/daikin/reyq8-48py1b/reyq8-48py1b_service-manual_502202428.webp)
Wiring Diagrams for Reference
SiBE37-701_B
417
Appendix
FXZQ20M / 25M / 32M / 40M / 50M9V1B
20, 25, 32, 40, 50 CLASS
(22, 28, 36, 45, 56 CLASS)
POWER SUPPLY
220-240V
~
50Hz
F2U
Q1DI
L
N
MAX.
300
A1P
A3P
A4P
X23A
X2A
X1A
SS1
SS2
(SEE NOTE 3)
H1P
H2P
H3P
H4P
X1A
BS1
L
N
X2M
RED
WHT
GRN/YLW
S1L
M
Y1E
X31A
X8A
F1U
R1T
t°
t°
R2T
X13A
X12A
X11A
R3T
X1A
T1R
KPR
X11A
X25A
X7A
YLW
YLW
M1P
M
X16A
X18A
HAP
X28A
X4A
V1TR
X30A
X23A
(SEE
NOTE 3)
A1P
PNK
WHT
YLW
ORG
BLU
BLK
T2
T1
F2
F1
P2
P1
X1M
RED
BLK
MSW
M1S
INPUT FROM OUTSIDE
(SEE NOTE 4)
TRANSMISSION WIRING CENTRAL
REMOTE CONTROLLER (SEE NOTE 2)
P2
P1
R1T
SS1
WIRED REMOTE
CONTROLLER
Q1M
M1F
M
C1
WH
T
YL
W
SWITCH BOX
X1M
A1P
C1
T1R
X2M
B
A1P
PRINTED CIRCUIT BOARD
T1R
TRANSFORMER (220-240V/22V)
H3P
LIGHT EMITTING DIODE
(FILTER SIGN-RED)
C1
CAPACITOR (M1F)
V1TR
TRIAC
F1U
FUSE ((B), 5A, 250V)
X1M
TERMINAL STRIP
H4P
LIGHT EMITTING DIODE
(DEFROST-ORANGE)
F2U
FIELD FUSE
X2M
TERMINAL STRIP
HAP
LIGHT EMITTING DIODE (SERVICE
MONITOR GREEN)
Y1E
ELECTRONIC EXPANSION VALVE
SS1
SELECTOR SWITCH (MAIN/SUB)
WIRED REMOTE CONTROLLER
SS2
SELECTOR SWITCH
(WIRELESS ADDRESS SET)
KPR
MAGNETIC RELAY (M1P)
R1T
THERMISTOR (AIR)
M1F
MOTOR (INDOOR FAN)
SS1
SELECTOR SWITCH (MAIN/SUB)
CONNECTOR FOR OPTIONAL PARTS
M1P
MOTOR (DRAIN PUMP)
WIRELESS REMOTE CONTROLLER
(RECEIVER/DISPLAY UNIT)
X16A
CONNECTOR
(ADAPTOR FOR WIRE)
M1S
MOTOR (SWING FLAP)
Q1DI
FIELD EARTH LEAK DETECTOR
(MAX. 300mA)
A3P
PRINTED CIRCUIT BOARD
X18A
CONNECTOR (ON/OFF)
(WIRING ADAPTOR FOR
ELECTRICAL APPENDICES)
A4P
PRINTED CIRCUIT BOARD
Q1M
THERMAL PROTECTOR
(M1F EMBEDDED)
BS1
PUSH BUTTON (ON/OFF)
H1P
LIGHT EMITTING DIODE
(ON-RED)
RED:RED
PNK:PINK
BLK:BLACK
ORG:ORANGE
WHT:WHITE
GRN:GREEN
YLW:YELLOW BLU:BLUE
R1T
THERMISTOR (AIR)
R2T
THERMISTOR (COIL-LIQUID)
H2P
LIGHT EMITTING DIODE
(TIMER-GREEN)
R3T
THERMISTOR (COIL-GAS)
S1L
FLOAT SWITCH
:
TERMINAL
: CONNECTOR
: WIRE CLAMP
: FIELD WIRING
NOTES:
1. IN CASE OF USING A REMOTE CONTROLLER, CONNECT IT TO THE UNIT IN ACCORDANCE TO THE ATTACHED INSTALLATION MANUAL.
2. X23A IS CONNECTED WHEN THE WIRELESS REMOTE CONTROLLER KIT IS BEING USED.
3. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FORCED OFF OR ON/OFF CONTROL OPERATION CAN BE SELECTED BY REMOTE CONTROLLER.
IN DETAILS, REFER TO THE INSTALLATION MANUAL ATTACHED TO THE UNIT.
4. REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM.
SEE TECHNICAL DATA AND CATALOGS, ETC. BEFORE CONNECTION.
3TW26426-1C
t°
t°
Содержание REYQ8-48PY1B
Страница 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Страница 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Страница 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Страница 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...