![Daikin REYQ8-48PY1B Скачать руководство пользователя страница 119](http://html.mh-extra.com/html/daikin/reyq8-48py1b/reyq8-48py1b_service-manual_502202119.webp)
SiBE37-701_B
Basic Control
Function
108
2.2
Compressor PI Control
Compressor PI Control
Carries out the compressor capacity PI control to maintain Te at constant during cooling
operation and Tc at constant during heating operation to ensure stable unit performance.
[Cooling operation]
[Heating operation]
Rotation of outdoor units
In order to make operating time equal for each compressor of multi connection outdoor units,
outdoor units are used in rotation.
However this is not applicable to single units.
[Rotation of outdoor units]
[System with two outdoor units]
[System with three outdoor units]
[Timing of outdoor rotation]
In start of startup control
Controls compressor capacity to adjust Te to
achieve target value (TeS).
Te : Low pressure equivalent saturation
temperature (°C)
Te set value (Make this setting while in Setting
mode 2.)
TeS : Target Te value
(Varies depending on Te setting, operating
frequency, etc.)
*On multi-outdoor-unit systems, this control is made
according to values of the first-priority unit, which is
detected with the pressure sensor.
Te setting
L
M (Normal)
(factory
setting)
H
3
6
7
8
9
10 11
Controls compressor capacity to adjust Tc to
achieve target value (TcS).
Tc : High pressure equivalent saturation
temperature (°C)
Te set value (Make this setting while in Setting
mode 2.)
TcS : Target Tc value
(Varies depending on Tc setting, operating
frequency, etc.)
*On multi-outdoor-unit systems, this control is made
according to values of the first-priority unit, which is
detected with the pressure sensor.
Tc setting
L
M (Normal)
(factory
setting)
H
43
46
48
Outdoor Unit 1
Outdoor Unit 2
Previous time
Priority 1
Priority 2
This time
Priority 2
Priority 1
Next time
Priority 1
Priority 2
Outdoor Unit 1
Outdoor Unit 2
Outdoor Unit 3
Previous time
Priority 1
Priority 2
Priority 3
This time
Priority 3
Priority 1
Priority 2
Next time
Priority 2
Priority 3
Priority 1
One time after the
next
Priority 1
Priority 2
Priority 3
Содержание REYQ8-48PY1B
Страница 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Страница 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Страница 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Страница 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...