SiBE37-701_B
Specifications
Specifications
56
Concealed Floor Standing Unit
1-2 ELECTRICAL SPECIFICATIONS
FXNQ20MAVE
FXNQ25MAVE
FXNQ32MAVE
FXNQ40MAVE
FXNQ50MAVE
FXNQ63MAVE
Power
Supply
Name
VE
Phase
1~
Frequency
Hz
50
Voltage
V
220-240
Current
Minimum circuit amps
(MCA)
A
0.3
0.3
0.6
0.6
0.6
0.6
Maximum fuse amps
(MFA)
A
15
15
15
15
15
15
Full load amps (FLA)
A
0.2
0.2
0.5
0.5
0.5
0.5
Voltage
range
Minimum
V
-10%
Maximum
V
+10%
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 × FLA
MFA is smaller than or equal to 4 × FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker