SiBE37-701_B
Special Control
Function
128
3.5
Pump down Residual Operation
3.5.1 Pump down Residual Operation in Cooling Operation
If the liquid refrigerant stays in the Evaporator at the startup of a compressor, this liquid refrigerant enters the
compressor, thus resulting in diluted oil in the compressor and then degraded lubrication performance.
Consequently, in order to recover the refrigerant in the Evaporator while the compressor stops, the pump-down residual
operation is conducted.
*
Pe_min and Pc_max indicate the minimum and maximum values in the system, respectively.
Actuator
Symbol
Elect.
symbol
Master unit operation
Slave unit operation
REYQ
REMQ
Compressor 1
—
M1C
M1C
124 Hz+OFF+OFF
OFF
Compressor 2
M2C
M2C
Compressor 3
M3C
M3C
Outdoor unit fan 1
—
M1F
M1F
Fan control
Fan control
Outdoor unit fan 2
M2F
M2F
Electronic expansion valve (Main) EVM
Y1E
Y3E
Y1E
1375 pls
1375 pls
Electronic expansion valve
(Subcooling)
EVT
Y2E
Y5E
Y3E
0 pls
0 pls
Electronic expansion valve
(Refrigerant charge)
EVJ
Y4E
Y2E
80 pls
80 pls
Four way valve (Heat exchanger
switch)
20SA
Y2S
Y9S
Y3S
OFF
OFF
Four way valve (Dual pressure gas
pipe switch)
20SB
Y8S
Y2S
ON
ON
Solenoid valve (Main bypass)
SVE
Y5S
Y10S
Y6S
ON
ON
Solenoid valve (Hot gas)
SVP
Y4S
Y5S
OFF
OFF
Solenoid valve (Refrigerant
regulator liquid pipe)
SVL
Y3S
Y4S
OFF
OFF
Solenoid valve (Refrigerant
regulator gas vent pipe)
SVG
Y1S
Y1S
OFF
OFF
Solenoid valve (Refrigerant
regulator discharge pipe)
SVO
Y7S
Y7S
OFF
OFF
Solenoid valve (Refrigerant
regulator discharge pipe)
SVT
Y6S
Y8S
OFF
OFF
Ending conditions
•
5 min.
•
Pe_min<0.49 MPa
∗
•
Pc_max<2.94 MPa
∗
•
Master unit Tdi>110
°
C
•
Master unit Tp>125
°
C
or
Содержание REYQ8-48PY1B
Страница 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Страница 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Страница 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Страница 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...