SiBE37-701_B
Field Setting
Test Operation
224
Image of operation in the case of A
Image of operation in the case of B
Image of operation in the case of A and B
Operation sound
Rated operation
sound
Operation sound
of level 1
Operation sound
of level 2
Operation sound
of level 3
Approx. 55 db (target)
(The power consumption may
be increased by about 10%.)
Approx. 50 db (target)
(The power consumption may
be increased by about 20%.)
Approx. 45 db (target)
(The power consumption may
be increased by about 30%.)
Note 1: Above values are reference only (measured in silent room)
Note 2: Above values are for 1 module only.
If capacity precedence is set in
“Capacity precedence setting”,
the fan speed will be increased
according to the load of air
conditioning when load is heavier.
Low noise mode instructing
Operation sound level set with “External low noise setting”
Operation sound during
low noise mode is
instructed can be set
with “External low noise
level setting”.
(Factory setting is “Mode
2”.)
(V3078)
Operation sound
Rated operation
sound
Operation sound
of level 1
Operation sound
of level 2
Operation sound
of level 3
Time set with “Night-time low noise start setting”
If capacity precedence is set in “Capacity
precedence setting”, the fan speed will
be increased according to the load of air
conditioning when load is heavier.
Time set with “Night-time low noise end setting”
Operation sound during
night-time low noise mode
is instructed can be set
with “Night-time low noise
level setting”.
(Factory setting is “OFF”.)
Night time
Operation sound level set with
“Night-time low noise setting”
Set with “Night-time low noise start setting”.
(Factory setting is “PM 10:00”.)
Set with “Night-time low noise end setting”.
(Factory setting is “AM 8:00”.)
PM 8:00
PM 10:00
PM 0:00
AM 6:00
AM 7:00
AM 8:00
(V3079)
Operation sound
Rated operation
sound
Operation sound
of level 1
Operation sound
of level 2
Operation sound
of level 3
Time set with “Night-time low noise start setting”
Low noise mode instructing
Operation sound set with
“External low noise setting”
If capacity precedence is set in “Capacity
precedence setting”, the fan speed will be
increased according to the load of air
conditioning when load is heavier.
Time set with “Night-time low noise end setting”
PM 8:00
PM 10:00
PM 0:00
Set with “Night-time low noise start setting”.
(Factory setting is “PM 10:00”.)
AM 6:00 AM 7:00 AM 8:00
Set with “Night-time low noise end setting”.
(Factory setting is “AM 8:00”.)
* Night time
* Operation sound
level set with
“Night-time low
noise setting”
* Operation sound set with
“External low noise setting”
Operation sound during low noise
mode is instructed can be set with
“External low noise level setting”.
(Factory setting is “Mode 2”.)
Operation sound during night-
time low noise mode is instructed
can be set with “Night-time low
noise level setting”.
(Factory setting is “OFF”.)
When external low noise
instruction is received during
the operation with night-time
low noise mode,
Mole 2 precedes Level 1 and
Level 3 precedes Level 2.
(V3080)
* Low noise mode
instructing
Содержание REYQ8-48PY1B
Страница 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Страница 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Страница 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Страница 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...