SiBE37-701_B
Field Setting
Test Operation
206
How to Select
Operation Mode
Whether operation by remote controller will be possible or not for turning on/off, controlling
temperature or setting operation mode is selected and decided by the operation mode given on
the right edge of the table below.
Do not select “timer operation possible by remote controller” if not using a remote controller.
Operation by timer is impossible in this case.
∗
1. Factory setting
Example
ON by remote
controller (Unified
ON by
centralized
remote controller)
OFF by remote
controller (Unified
OFF by
centralized remote
controller)
OFF by
remote
controller
Temperature
control by
remote controller
Operation mode
setting by
remote controller
Control
mode is "1."
↓
Rejection
↓
Rejection
↓
Rejection
↓
Acceptance
↓
Acceptance
(VL069)
Control mode
Control by remote controller
Control mode
Operation
OFF
Temperature
control
Operation
mode setting
Unified operation,
individual operation
by centralized remote
controller, or
operation controlled
by timer
Unified OFF,
individual stop by
centralized remote
controller, or timer
stop
ON/OFF control
impossible by
remote controller
Rejection (Example)
Rejection (Example)
Rejection
(Example)
Rejection
Acceptance
0
Rejection
10
Acceptance
(Example)
Acceptance
(Example)
1(Example)
Rejection
11
OFF control only
possible by
remote controller
Acceptance
Rejection
Acceptance
2
Rejection
12
Acceptance
Acceptance
3
Rejection
13
Centralized
Acceptance
Rejection
Acceptance
4
Rejection
14
Acceptance
Acceptance
5
Rejection
15
Individual
Acceptance
Rejection
Acceptance
6
Rejection
16
Acceptance
Acceptance
7
∗
1
Rejection
17
Timer operation
possible by
remote controller
Acceptance
(During timer at ON
position only)
Acceptance
(During timer at ON
position only)
Rejection
Acceptance
8
Rejection
18
Acceptance
Acceptance
9
Rejection
19
Centralized remote controller
When ON/OFF, temperature setting and
operation mode setting by local remote
controller is forbidden, "UNDER
CENTRALIZED CONTROL" is displayed
on the remote controller.
Содержание REYQ8-48PY1B
Страница 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Страница 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Страница 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Страница 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...