SiBE37-701_B
Field Setting
Test Operation
192
<Setting confirmation screen>
(6)
Press Menu/Enter button. Setting
confirmation screen is displayed.
6
(7)
Press Menu/Enter button.
Setting confirmation
7
Select
Yes
and press Menu/
Enter button. Setting details are
determined and field setting list
screen returns.
8
In the case of multiple setting
changes, repeat “ (3) ” to “ (7) ”.
9
After all setting changes are com-
pleted, press Cancel button twice.
CAUTION
Backlight goes out, and
“Connection under check Please
wait for a moment” is displayed for
initialization. After the initialization,
the basic screen returns.
z
When an optional accessory is installed on the indoor unit, settings of the indoor unit may be
changed. See the manual of the optional accessory.
z
For field setting details of the outdoor unit, see installation manual attached to the outdoor unit.
10